HEATING: gas burner
GAS BURNER TROUBLESHOUTING
If faults reported on CLIMATIC
-Reset the CLIMATIC.
-Check voltage: 230V after circuit breaker.
-Check GAS isolation shut-off valves are open.
-Check GAS pressure at the inlet of the GAS valves. It must be >20 mbar when the Burners shut down.
-Adjust the set points to priorities the burner. Increase the value of the room temperature set point to a temperature higher
than actual room temperature.
Table 6
STAGE
NORMAL
Heating
Contactors
Requested
engaged
Contactors
Extraction Fans
are
are
engaged
running
After 30 to 45
Extraction
seconds :
fan is
pre-ventilation the
ON
fire-up electrode
should spark
Continuous
After a few
ventilation
seconds the
and sparks
gas burner
from fire up
fires-up
electrode
Page 50 - IOM / ROOFTOP BALTIC Series - 0803 - E
POSSIBLE
OPERATION
Contactors do
+ Check "Safety Thermostats" In the air flow
not engage
before the gas heat exchanger.
+ Check the free movement of the fan wheel
+ Check the supply temperature limitation thermostats
+ Check gas low pressure switch
Nothing
+ Check electrical connection on the gas
happens
Ignition Control Block and on
connection board
+ Check the fan voltage supply voltage
+ Check the fire-up electrode
Continuous
+ Check the pressure drop at the pressure
ventilation
switch : It must be higher than 165 Pa
happens
+ Check the good operation of the pressure
without sparks
switch using an Ohmmeter and by artificially
from fire-up
creating a depression in the tube.
electrode
+ Check the operation the Backfire thermostat.
After 4 seconds
+ Check injection pressure during start-up
the GAS burner
(value for High Heat)
still not operating
+ Check the supply voltage to the ignition
and safety shutdown control box (continuous voltage)
by the ignition
+ Remove the control box from the gas block.
Control Block.
Within 4 seconds
+ Check that the High / Low control is
the GAS burner
connected (for valve VK 4125 P).
fires-up BUT
+ Check the position and connections of the
safety shutdown
Ionisation Probe. It must not be Earthed (230 V) + Adjust the supply and
from the ignition
+ Check the Polarity of the 230 V connection
Control Block.
on the gas burner transformer.
+ Measure the Ionisation Current : It must be
higher than 1,5 microAmps.
+ Check the type of gas.
ACTION
FAULT
POSSIBLE
SOLUTION
Replace
component
+ Replace thermostat
+ Open gas supply
+ Replace connection
board if necessary
+ Re-position the pressure
switch tube
+ Change the pressure
switch
+ Reset or replace the
Thermostat
+ Remove the air from the
gas pipe-work
+ Adjust the injection
pressure to high heat value.
+ Change the control box
if the gas valve is OK.
+ Change the gas valve.
+ Check the whole
electrical supply.
injection pressure if gas is
different from natural
gas G20 : ( G25 gas of
Groningue for example).