Main Screen Code
Description
Code Description Code Description
4-Ventilation
Code UNIT
5-Enable
3350 1-Fan On/Off
3351
2-Fan Dead
3352
3-F.Air
3353
4-CO2
3354
5-Comp.Cool. 3355
6-Comp.Heat. 3356
7-AuxHeat
3357
8-Humidif.
3358
9-Low Noise
3359
6-Capacity
3360 1-Room
3361 ~
2-Reheat
3362 ~
7-Safety
3370 1-Room Low
3371 °C
2-Room High 3372 °C
3-Sup.Lo.1
3373 °C
4-Sup.Lo.2
3374 °C
5-Sup.Lo.3
3375 °C
6-Sup.Hi.1
3376 °C
7-Sup.Hi.2
3377 °C
8-Room Low
3378 %
9-Room High 3379 %
3410 1-Air Flow
3411 Pa 0
Min
Factory Max
description
(1)
*[Enable] Stopping and running of the Fan Blower.[OFF] the
On/Off
~
On
~
blower is stopped, [ON] the blower is running.
(1)
*[Enable] Stopping and running of the fan in the "Control
On/Off
~
On
~
Dead Zone". [OFF] the blower is stopped, [ON] the blower is
running.
*[Enable] Run eco: [ON] the Economiser is running, [OFF]
(1)
On/Off
~
On
~
the Economiser if stopped.
*[Enable] Run CO2 Sensor: [ON] Switch-on the CO2 on a
(1)
On/Off
~
On
~
Zone, [OFF]Stop the CO2 sensor on a zone.
(1)
*[Enable] [OFF] Force the unloading of compressors in
On/Off
~
On
~
cooling mode.
*[Enable] [OFF] Force the unloading of compressors in
(1)
On/Off
~
On
~
heating mode.
(1)
*[Enable] [OFF] Force the unloading of heating module
On/Off
~
On
~
(electric, gas or heat water coil)
(1)
*[Enable] [OFF] Force the unloading of humidity control.
On/Off
~
On
~
(1)
On/Off
~
Off
~
*[Enable] Force the noise reduction mode. [ON] 50% of the
compressors are unloaded in "Unocupied" zone
1
4
100
*[Capacity Factor] Reactivity : Refer to "Climatic features" in
*IOM for details
1
4
100
*[Capacity Factor] Reactivity: Refer to "Climatic features" in
*IOM for details
5
5
20
*[Safety Limit] Room temperature "Low Limit" in °C Threshold
of activation of an alarm
20 40
40
*[Safety Limit] Room temperature "High Limit" in °C
Threshold of activation of an alarm
9 or 5
10 or 8 19
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 1° level of security: Reduce the
"Capacity Factor" by one stage of compressor and switch to
minimum Fresh Air,
7 or 3
8 or 6
17
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 2° level of security: Reduce the
"Capacity Factor" to zero and switch to 0% Fresh Air,open the
HWC valve.
5 or 1
6 or 2
15
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 3° level of security. - Alarm
threshold, the unit is switched off.
20 40
70
*[Safety Limit] Supply temperature high Limit (in °c) -
Threshold of activation of the 1° level of security: reduce the
capacity factor by one stage of compressor. Close the HWC
valve.
20 60
70
*[Safety Limit] Supply temperature high Limit (in °c) -
Threshold of activation of the 2° level of security: Alarm
threshold: Reduce the capacity factor to 0
0
0
100
*[Safety Limit] Room relative humidity low Limit (in %) -
Threshold of activation of the alarm
0
100
100
*[Safety Limit] Room humidity high Limit (in %) - Threshold of
activation of the alarm
25
1000
*[Safety Limit] Airflow Detection Threshold of pressure
difference in Pa indicating Low Airflow Rate. If the pressure
difference across the filter is lower than this threshold the
safety is activated.