9 Diagnosis, asset management and service

Maintenance

Measured value memory
Event memory
52
9
Diagnosis, asset management and service
9.1
Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
In some applications, product buildup on the diaphragm can influence
the measuring result. Depending on the sensor and application, take
precautions to ensure that heavy buildup, and especially a hardening
thereof, is avoided.
9.2

Diagnosis memory

The instrument has several memories which are available for diagno-
sis purposes. The data remain even with voltage interruption.
Up to 100,000 measured values can be stored in the sensor in a ring
memory. Each entry contains date/time as well as the respective
measured value.
Depending on the instrument version, values that can be stored are
for example:
Pressure
Differential pressure
Level
Flow
Density
Interface
Percentage value
Lin. percent
Scaled values
Measuring cell temperature
Electronics temperature
When the instrument is shipped, the measured value memory is
active, saving distance, measurement certainty and electronics tem-
perature every minute.
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Up to 500 events are automatically stored with a time stamp in the
sensor (non-deletable). Each entry contains date/time, event type,
event description and value. Event types are for example:
Modification of a parameter
Switch-on and switch-off times
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
VEGABAR 81 • Profibus PA