General Specifications; Input Specifications - IAI PSA-24 Instruction Manual

24v power supply unit
Hide thumbs Also See for PSA-24:
Table of Contents

Advertisement

1.2 General Specifications

1.2 General Specifications

Input specifications

Item
Power input voltage
range
Power supply
current
Power frequency
range
*1
Inrush current
Momentary power
failure resistance
Electric shock
protection
mechanism
Efficiency
Power factor
*1: The pulse width of flowing inrush current is less than 5 ms. In parallel operation, inrush
current increases according to the number of units. Check the characteristics thoroughly
before selection to prevent the breaker from tripping due to inrush current.
1-3
Specifications
100 VAC to 230 VAC ±10%
2.5A or less
100 VAC
3.9A or less
1.4A or less
200 VAC
1.9A or less
50/60Hz ±5%
100 VAC
200 VAC
100 VAC
27.4A (typ)
200 VAC
54.8A (typ)
50 Hz
60 Hz
Class I
100 VAC
86% or more
200 VAC
90% or more
100 VAC
99% (typ)
200 VAC
90% (typ)
Terms of use, etc.
Continuous rated
output 204 W
Continuous rated
output 330 W
Continuous rated
output 204 W
Continuous rated
output 330 W
17A (typ)
At cold start (25°C)
34A (typ)
At cold start (40°C)
20ms
16ms
Continuous rated
output 204 W
Continuous rated
output 204 W

Advertisement