CAUTION:
Combustion
contaminated by corrosive chemical fumes which
can damage the boiler and void the warranty.
a. All Air From Inside The Building:
Each opening shall have a minimum net free
square inches as noted in Table E.
Model
Sq. Inches
133
136
182/181
181
260/261
264
330/331
334
400/401
399
514
512
624
627
724
726
824
825
962
962
Table E: Minimum Net Free Air from Inside Building
b. All Air From Outdoors:
When air is supplied directly from outside of build-
ing, each opening shall have a minimum net free
square inches as noted in Table F.
Model
Sq. Inches
133
34
182/181
46
260/261
66
330/331
84
400/401
100
514
128
624
157
724
182
824
207
962
241
Table F: Minimum Net Free Air from Outside Building
air
must
not
be
Model
Sq. Inches
1125
1125
1223
1223
1336
1337
1468
1467
1631
1630
1826
1826
2100
2100
2500
2499
3001
3000
3500
3500
4001
4000
Model
Sq. Inches
1125
282
1223
306
1336
335
1468
367
1631
408
1826
457
2100
525
2500
625
3001
750
3500
875
4001
1000

Venting

Outdoor Installations
Model 133
1. Remove the front (4) screws.
2. Line up outdoor top vent opening over heater vent
opening.
3. Lower outdoor top onto unit lining up slots in the
outdoor top with screw holes in jacket top.
4. Reinstall (5) screws to secure jacket top and out-
door top to unit.
Fig. 4: Installing Outdoor Top—Model 133
Models 181-401 & 182-400
Outdoor Top Installation
Fig. 5: Installing Outdoor Top—Models 181-401 & 182-
9
(Part of heater)
400