Download Print this page
Raypak 182-400 Specification Sheet
Raypak 182-400 Specification Sheet

Raypak 182-400 Specification Sheet

Raypak hydronic heating boilers specification sheet

Advertisement

Quick Links

Job:
Engineer:
Contractor:
Prepared By:
Model:
EFFICIENT
82% efficiency – highest of any atmospheric boiler
available today
THERMAL SHOCK PROOF
Twenty-year warranty against thermal shock damage
up to 150°F differential
Maximum operating temperature: 230°F
LIGHTWEIGHT
A floor load of 70 lbs./sq. ft. or less
HIGH RECOVERY
Cuts fuel costs substantially because the standby and
radiation losses normal to other boilers and
tank-type water heaters are eliminated
LOW WATER OPERATING TEMPERATURE
Operates with water temperature as low as
105°F without condensing
Heat Exchanger
ASME Inspected and Stamped
160 PSIG
National Board Approved
Headers
Cast Iron Glass-lined – Standard
Bronze – Option A-1
Finned Tubing
Copper – Standard
Cupro Nickel – Option A-3
ASME Steel Tube Sheet
Silicone O-Rings
ASME Pressure Relief Valve
45 PSIG – Standard
PSIG ASME – Optional
Temperature and Pressure Gauge,
Shipped Loose
Water Connections
Left Hand – Standard
Right Hand – Option A-6
Flow Configuration – Two-pass
Pump – Optional
Mounted, 1/8 HP, 120 Volt, 1∅, 60 Hz
Controls
120V, 60Hz, 1 Ph Power Supply
120/24V Transformer
100% Pilot Shut-off/Lockout
Electronic, Intermittent Ignition (IID) Pilot
High Limit Control, Manual Reset
On/Off Switch
Flow Switch
Economaster II Pump Time Delay
Catalog No.: 2000.205D
Date:
Indoor
Gas Control Train
Manual Main Gas Shut-off Cock
Main Gas Pressure Regulator
Redundant Safety Shut-off Valve
Control Valve
Firing Mode
On/Off (H4)
Two-stage Firing (H3)
Mechanical Modulation,
110-170°F (H5)
Mechanical Modulation,
150-210°F (H1)
Fuel
Natural Gas
Propane Gas
Design Certified ANSI Z21.13
Construction
Front Controls
Stainless Steel Burners
Polytuf Powder Coat Finish
Vent Selection
Draft Diverter – Option D-10
Power Vent, Loose – Option D-2
Base (Optional)
Combustible Floor Shield –
Option J-1
Effective: 1-1-08
Replaces: 4-1-05
®
Raytherm
Hydronic Heating Boilers
Models 182-400 - Indoor
Temperature Controls
Note: H1 and H5 do not require a
controller
B-6
Two-stage – 100-200ºF
Y-241 Electronic Sequencer,
1-4 Stages
Y-281 Electronic Sequencer,
1-8 Stages
Additional Safety Controls
F-10 Low Water Cut-off Probe
I-1
High Limit Control, Auto
Reset, 240°F
S-1
Low Gas Pressure Switch,
Manual
S-2
High Gas Pressure Switch,
Manual
Regulatory Agency Requirements
- Type H

Advertisement

loading

Summary of Contents for Raypak 182-400

  • Page 1 Power Vent, Loose – Option D-2 Base (Optional) Combustible Floor Shield – Option J-1 Replaces: 4-1-05 ® - Type H Models 182-400 - Indoor Temperature Controls Note: H1 and H5 do not require a controller Two-stage – 100-200ºF Y-241 Electronic Sequencer, 1-4 Stages...
  • Page 2 NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each 1,000 feet above sea level. Model H-182 H-260 H-330 H-400 N/A – Not Applicable Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 Catalog No.: 2000.205D Effective: 1-1-08 (OPTIONAL) PUMP COVER (OPTIONAL) (OUTDOOR...

This manual is also suitable for:

H-182H-260H-330H-400