Functional specification:
Item
Input Signal Type
Control Method
Freq. Range
Resolution Setting
Freq.
Control
Keyboard Setting
External Signal Setting
Other function
Carrier frequency
Accelerate/Decelerate time
V/F Pattern
General
Torque control
Control
Multi-Functional input
Multi-Functional output
Braking Torque
Other function
Display
Operating temperature
Humidity
Vibration
EMC specification
UL
Overload protection
Over-voltage
Under voltage
Protection
Momentary Power-loss
Function
Stall Prevention
Output Short-circuit
Grounding fault
Other function
Installation
PNP type (SOURCE) input (External 24VDC Input is allowed)
Sinusoidal wave PWM control
1~200 Hz
Digital: 0.1 Hz (1 ~ 99.9 Hz); 1 Hz (100 ~ 200 Hz)
Analog: 1Hz/ 60 Hz
Directly setup by
and
0~10V, 4 ~ 20mA, 0 ~ 20mA
Frequency upper and lower limit
4~16KHz
0.1~ 999 Sec
6 Patterns
Torque boost level adjustable (manual torque boost)
2 point, to be used as multi-speed 1(Sp.1) / multi-speed 2(Sp.2) /
Jog / External quickstop / External bb / Reset
1a Relay terminal, to be setup as Fault / Running / Frequency.
S115, S220 01, 03 and 05: about 20%
S220 07, 09 and T400: 20%~100% built-in braking transistor
Decelerate or free run stop, Auto reset, DC braking frequency /
Voltage / Time can be setup by constants.
Three digital LED display frequency / inverter parameter / fault
record / program version.
O
C ~ +40
C (with cover removed: -10
O
-10
0~95% RH non-condensing.
2
Under 1 G (9.8 m/s
)
EN50081-1, EN50081-2, EN50082-2, EN50178, EN61800-3+A11
UL508C
150% for 1 min.
DC voltage > 410V(200 series); DC voltage > 800V(400 series)
DC voltage < 200V(200 series); DC voltage < 400V(400 series)
0 ~ 2 sec: the inverter can be restarted using speed search
feature.
During Acceleration / Deceleration/ Constant speed
Electronic circuitry protection
Electronic circuitry protection
Heat sink overheat protection, Current limit
Mounting screw or DIN rail (Option).
10
10
Specification
buttons.
O
C ~ +50
O
C)
Need help?
Do you have a question about the Vectron Syn10 S115 01 and is the answer not in the manual?
Questions and answers