Clearances To Combustibles - Re-Verber-Ray XTS3-20-60 Insert Manual

Xts3 series
Table of Contents

Advertisement

1.0
Safety • Safety Labels and Locations • Clearance to Combustibles
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
F/N: LLTB026
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Disconnect gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
SERVICE ACCESS PANEL
F/N: LLTB025R
F/N: LL01 - Clearance Safety Tag
(Affix adjacent to heater's thermostat)
Clearance to Combustibles
Clearance to combustibles is defined as the minimum distance that must exist between the tube surface,
or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that must be
maintained from moving objects around the tube heater.
When installing the tube heater system, clearances to combustibles for the Series tube heater and
configuration must be maintained. Refer to Chart 1.1 on the following page to determine the required
distances for your model.
SERVICE ACCESS PANEL
F/N: LLTB024L
RE-VERBER-RAY INFRA-RED RADIANT TUBE HEATER
®
FOR OUTDOOR USE AND INDOOR (Non-Residential) INSTALLATION ONLY.
Class IIIA Permanent Label
MODEL NO.
INPUT BTU/H
FOR USE WITH
XTS-40-125N(-3)
125,000 / 95,000
Natural Gas
Volts AC:
Manifold Pressure:
Heater Type
120V - 60Hz
3.5 in.
W.C.P.
C1
AMPS - Starting:
Maximum Inlet Pressure:
Minimum Mounting Angle:
4.8
14 in.
W.C.P.
0
DEGREES
AMPS - Running:
Minimum Inlet Pressure:
Maximum Mounting Angle:
1.1
5.0 in.
W.C.P.
45
DEGREES
Combustion Chamber:
4" Black Coated Aluminized
For stainless steel upgrades: The combustion tube is 409 Series stainless steel.
DESIGN COMPLIES WITH:
ANSI Z83.20b-2004-GAS FIRED LOW INTENSITY INFRA-RED HTR.
DETROIT RADIANT PRODUCTS COMPANY
Serial No.: 0807XXXXXXXXXX 0001
21400 HOOVER ROAD - WARREN, MI
(586) 756-0950
-
www.drp-co.com
Control Compartment
16" Burner
Tube
Fan
Compartment
WARNING
!
Placement of explosive objects, flammable objects, liquids and vapors close to
the heater may result in explosion, fire, property damage, serious injury or
death. Do not store or use explosive objects, liquids and vapor in the vicinity of
the heater.
HL-40-125N(-3)
XTS
Production Code:
XTS3
HL3-125
Version:
7.08
Data on this label is for the model shown on this label. If your heater has been converted,
this information is not accurate. Please contact the factory for assistance.
BURNER COMPONENTS:
Gas Valve:
36G54-224-N
Circuit Board:
35-66
Wire Harness:
3 PCS Harness
N.O. Switch:
None
N.O. VL Orifice:
None
N.C. Switch:
None
N.C. VL Orifice:
None
Diff Switch:
IS22010051F5166
Diff VL Orifice:
Grey (+ / -)
Igniter:
Norton
Burner:
Mid
16" Tube:
4" Gen.
Ind. Lights:
Yellow - 24V
HEATER
Orifice Type:
TYPE:
Gas:
TP-204#
C1
Air:
TP-44#
For parts replacement information, contact factory at 586-756-0950 or visit www.drp-co.com/parts.
Burner Control Box Component Label
(located inside the center compartment lid)
®
MODEL NO.
XTS
HL-40-125N(-3)
Volts AC:
120V - 60Hz
AMPS - Starting:
4.8
AMPS - Running:
1.1
Combustion Chamber:
4" Black Coated Aluminized
DESIGN COMPLIES WITH:
ANSI Z83.20b-2004-GAS FIRED LOW INTENSITY INFRA-RED HTR.
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI
(586) 756-0950
-
Primary Combustion
Chamber
INSTALLER
!
AVOID EQUIPMENT FAILURE
THIS 10 FT. TUBE IS THE
COMBUSTION CHAMBER.
The combustion chamber utilizes either 409
stainless, titanium alloy or aluminized steel -
depending on the model number of your heater.
Rotate the tube's welded seam to bottom.
Consult the manual(s) for further details.
F/N: LLTB004
(orange)
4
XTS3
Serial No.: 0804XXXXXXXXXX 0001
Stock:
None
Add-On:
N/A
(Specify TP-#'s)
840A
Diag. Light:
On Circuit Board
851B
Term. Block:
None
N/A
3252
Transformer:
40 VA
826
N/A
Fan:
Fasco Lg.
55A
Alt. Fan:
50Hz - 120V
55B
N/A
Alt. Fan Usage:
When Specified
Relay:
Picker x2
1325
Filter:
264E
None
N/A
24 Volt In:
3 T-plug
832
50
120 Volt In:
6' Blk. Cord
333
201B
Gas In:
7/8" FC
83
380
Extra VL Orifice:
None
828
Internal Use Only:
C1
C2
C3
Electric:
Special 1:
19
19
19
LLWT038
17
Tag:
1 5/16"
1 7/16"
1 5/16"
None
Special 2:
1 7/16"
RE-VERBER-RAY INFRA-RED RADIANT TUBE HEATER
FOR OUTDOOR USE AND INDOOR (Non-Residential) INSTALLATION ONLY.
Class IIIA Permanent Label
INPUT BTU/H
FOR USE WITH
125,000 / 95,000
Natural Gas
Manifold Pressure:
Heater Type
3.5 in.
W.C.P.
C1
Maximum Inlet Pressure:
Minimum Mounting Angle:
14 in.
W.C.P.
0
DEGREES
Minimum Inlet Pressure:
Maximum Mounting Angle:
5.0 in.
W.C.P.
45
DEGREES
For stainless steel upgrades: The combustion tube is 409 Series stainless steel.
Serial No.: 0807XXXXXXXXXX 0001
www.drp-co.com
Secondary Combustion
Chamber (if applicable)
ALUMINIZED TUBE
(This is the Second Chamber)
This tube is constructed of aluminized coated steel and must be
placed directly after the titanium coated "Combustion Chamber"
(orange labeled tube).
150,000 to 200,000 BTU/h
models only