Conduit Adapters

Step
Remove the protective plastic cap from the threaded conduit entry.
1
To ensure the environmental ingress rating on tapered threads (NPT),
2
a non-hardening thread sealant may be used.
Thread the appropriate size adapter (M20 or ½" NPT) into the conduit
3
entry opening
Tighten adapters according to the following torque:
4
Torque: 32 Nm or 24 lb-ft.
Note: Plugs do not come installed in the housings. All housings come with
temporary plastic dust protectors (red or blue) installed and are not certified for use
in any installation.

WIRING

HART / 4-20mA Operating Ranges
The transmitter is designed to operate in a two-wire / current loop with loop resistance and
power supply voltage within the operating range for HART / 4-20 mA installations as
described in
Figure 17.
Note: A minimum of 250 Ohms of loop resistance is required to support HART
communications.
�������� �������������������� = �������������� �������������������� + �������� �������������������� + ���������������� ��������������������
For all HART installations, Honeywell recommends the HART resistor to be placed on
the positive side. Voltage should not exceed 42 VDC. See the process design system
documentation for specifics.
December 2017
Wiring must comply with local codes, regulations and ordinances.
Grounding may be required to meet various approval body
certification, for example CE conformity.
Refer to the SmartLine Level Guided Wave Radar User's Manual,
Document #34-SL-25-11.
Supply Voltage
(Vdc)
14
19.5
24
30
34
40
42
Quick Start Installation Guide
Action
Max. Loop
Resistance (Ohms)
0
250
459
750
917
1200
1284
27