Figure 19: Hart Jumper Location - Honeywell SLG 700 Quick Start Manual

Smartline level guided wave radar
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Step
1
2
3
4
5
6
32
ATTENTION: Electrostatic Discharge (ESD) hazards.
Observe precautions for handling electrostatic sensitive
devices.
Turn OFF Transmitter power.
Loosen the end-cap lock, and unscrew the end cap from the
Electronics side of t-he Transmitter housing.
If applicable, carefully depress the tabs on the sides of the
Display Module and pull it off.
If necessary, move the interface connector from the
Communication Module to the display module to provide the
preferred orientation of the display module in the window.
Set the Failsafe Jumper (top jumper) to the desired action
(UP or DOWN). And the Write Protect jumper (Bottom
jumper) to the desired behavior (Protected or Unprotected)
See
Screw on the end-cap and tighten the end-cap lock.
8
Table
for jumper positioning.
Turn ON Transmitter power.

Figure 19: HART Jumper Location

Quick Start Installation Guide
Action
December 2017