Control Techniques AXIMA 2000 Installation Manual page 27

Multi-axis controller
Table of Contents

Advertisement

and 40 Amps at 230 VAC for 2 milliseconds. This inrush current must be considered when
choosing AC power fusing.
Note
The AC Power removable connector terminals are to be torqued 6 to 7 inch pounds at
installation of wiring.
Figure 8:
AC Supply
Voltage
115 VAC
1 Amp
230 VAC
0.5 Amp
External Fusing Requirement
The AC power supply must be fused with a 2 amp fuse in each ungrounded line. A grounded
line (neutral) must not be fused. Littelfuse
can be used.
AC Power Connector
Inrush Current
Current
(2 ms)
20 Amps
40 Amps
Fusing
Frequency (Hz)
FLM-2 or equivalent
50/60
2 Amp Slo-Blo
®
's FLM-2 SLO-BLO type fuse, or an equivalent,
Installation
AC Supply Limit
96 to 264 VAC
15