Air to Water Heat Pump (Split integrated DHW type)
Line
Function
Heating adjustment, circuit 1
710
U
Comfort setpoint
U
712
Reduced setpoint
U
714
Frost protection setpoint
716
S
Comfort setpoint maximum
720
I
Heating curve slope
(see section
I
721
Off-set of the heating curve
730
I
Summer / Winter heating limits
When the average of the Outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating
(as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode.
740
I
Flow temp setpoint min
(with dynamic radiator, adjust from 30 to 35°C)
I
741
Flow temp setpoint max
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note : Maximum temperature limitation is not a safety function as required by ground heating.
750
S
Room influence
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
760
S
Room temperature limitation
As soon as the room temperature = [Setpoint line 710 (ex. 20°C) + Room temperature limitation setpoint line 760
(ex. 0,5 °C)] > 20,5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room temperature < 20,0 °C).
780
S
Quick setback
790
S
Optimum start control max
(Early start to switch to the comfort setting.)
791
S
Optimum stop control max (Early stop to switch from
the comfort setting to the reduced setting.)
800
S
Reduced setpoint increase start
801
S
Reduced setpoint increase end
830
S
Mixer valve boost
834
S
Actuator running time
Installation and operating manual "1768 - EN"
7.4.3, page 46
&
figure 47, page
(figure 48, page
Setting range
or display
Reduced setpoint...
Comfort setpoint maximum
Frost protection setpoint...
Comfort setpoint
4 °C... Reduced setpoint
20 °C
35 °C
0,1... 4
45)
45)
-4,5 °C... 4,5 °C
8 °C
30 °C
8 °C... Flow temp setpoint max
Flow temp setpoint min... 70 °C
1%... 100%
0,5... 4 °C
Off, Down to reduced setpoint,
Down to frost prot setpoint
0... 360 min
0... 360 min
-30... 10 °C
-30... 10 °C
0
50 °C
30... 873 s
Setting
Basic
increment
setting
0,5 °C
20 °C
19 °C
0,5 °C
8 °C
0,5 °C
1 °C
28 °C
0,02
0,5
0
0,5 °C
0,5 °C
18 °C
1 °C
17 °C
60 °C
1 °C
1%
50%
0,5 °C
0,5 °C
Off
180 min
10 min
30 min
10 min
1 °C
--
1 °C
-5 °C
1 °C
0 °C
1 s
240 s
- 49 -