Fujitsu Waterstage WOYG112LCTA Maintenance Document page 52

Air to water heat pump split integrated dhw type
Hide thumbs Also See for Waterstage WOYG112LCTA:
Table of Contents

Advertisement

Air to Water Heat Pump (Split integrated DHW type)
Line
Function
1150
I
Floor curing function
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
1151
I
Floor curing setpoint manually
(if line 1150 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying program stops automatically after running for 25 days.
1156
I
Floor curing day current
1157
I
Floor curing day completed
S
1200
Operating mode changeover
Operating mode at end of concrete slab drying period.
Cooling circuit 2
If the installation is fitted with the cooling kit (Only with the cooling kit option).
1201
U
Operating mode
1202
U
Comfort cooling setpoint
U
1203
Reduced setpoint
1208
I
Flow temp setp at OT° 25°C
1209
I
Flow temp setp at OT° 35°C
1212
I
Cooling limit at OT°
S
1213
Lock time at end of heating / cooling
1218
S
Summer comp start at OT°
1219
S
Summer comp end at OT°
1220
S
Summer comp setp increase
S
1223
Flow temp setp min OT° 25°C
1224
S
Flow temp setp min OT° 35°C
1228
S
Room influence
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
S
1232
Room temp limitation
1238
S
Mixing valve decrease
1241
S
Actuator running time
1263
S
With prim contr / system pump
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
- 52 -
(figure 50, page
50)
Setting range
or display
0
95 °C
0
32
0
32
None, Protection mode,
Reduced, Comfort, Automatic
Protection, Automatic, Reduced,
Comfort
17
40 °C
5 40°C
6
35 °C
6
35 °C
8
35 °C
8
100
20
50 °C
20
50 °C
1
10 °C
6
35 °C
6
35 °C
1... 100 %
0,5... 4 °C
0
20 °C
30... 873 s
No, Yes
Installation and operating manual "1768 - EN"
Setting
Basic
increment
setting
Off
1 °C
25 °C
0
Reduced
Protection
0,5 °C
24 °C
26 °C
0,5 °C
20 °C
0,5 °C
16 °C
0,5 °C
24 °C
24 h
1 h
1 °C
26 °C
1 °C
40 °C
1 °C
4 °C
18 °C
0,5 °C
0,5 °C
18 °C
1 %
80 %
0,5 °C
0,5 °C
1 °C
0 °C
1 s
240 s
No*