Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Set Point Profile Segments
The table below describes the registers that are part of a setpoint profile segment. A profile contains up to
50 segments and each segment consumes 8 registers, therefore each profile uses 400 contiguous registers.
To determine the actual register address for a parameter within a segment, add the register offset to the start
address of the segment. This table contains fixed addresses of SP Programmer #1 Segments; see Table 6-1
for starting addresses of other SP Programmer Segments.
The addresses given in Table 6-10 do not necessarily apply to segments in the custom map. For custom
addresses view or print a report in HC Designer.
Fixed
Fixed
Register
Address
Register
Offset
(Hex)
(Decimal)
2800
10241
0
2801
10242
1
2802
10243
2
2804
10245
4
2806
10247
6
2808
10249
8
.
.
.
.
.
.
.
.
.
298E
10639
398
62

Table 6-10 SP Programmer Segments

Parameter
Segment #1 Ramp/Soak
Segment
Guaranteed Soak Enable
Segment #1 Events
Segment #1 Time or Rate
Segment #1 Ramp or Soak
value
Segment #1 Soak value for
auxiliary output (use "Time
or Rate" for duration)
Segment #2 Ramp/Soak
Segment
Guaranteed Soak Enable
.
.
.
Segment #50 Soak value
for auxiliary output (use
"Time or Rate" for
duration)
HC900 Process Controller Communications User Guide
Access Notes
R/W
Bit Packed
Bit 0: 1 = ramp segment; 0=soak segment
Bit 1: 1 = guaranteed soak enabled
0 = guaranteed soak disabled
Bit 0 is ignored in the hold mode.
Writing to this register is not permissible in
the run mode.
R/W
Bit Packed
Bit 0: Event #1
:
:
Bit 15: Event #16
0: Event OFF 1: Event ON
Writing to this register is only permissible in
reset or ready mode.
R/W
Floating Point in time units configured for the
set point programmer
Writing to this register is not permissible in
the run mode.
R/W
Floating Point
Writing to this register is not permissible in
the run mode.
R/W
Floating Point
Writing to this register is not permissible in
the run mode.
R/W
Bit Packed
Bit 0: 1 = ramp segment; 0=soak segment
Bit 1: 1 = guaranteed soak enabled
0 = guaranteed soak disabled
Bit 0 is ignored in the hold mode.
Writing to this register is not permissible in
the run mode.
.
.
.
.
.
.
R/W
Floating Point
Writing to this register is not permissible in
the run mode.
Revision 13
April 2017