Time; Table 6-6 Time Parameters - Honeywell HC900 User Manual

Process controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Parameters accessible with Function Code 03, 06,10h

Time

Example
Query: Read Variables 1 and 2 from HC900 at address 1 using Function Code 3 (hex codes).
TCP:
00
03
RTU:
01
03
Response: from HC900 where Variable 1 = 100.0 and Variable 2 = 55.32
TCP:
00
03
RTU:
01
03
6.7 Time
The addresses given in Table 6-6 do not necessarily apply to time parameters in the custom map. For
custom addresses view or print a report in HC Designer.
In HC Designer's custom map these parameters are grouped under the Item Filter "System Parameters."
You must add them all to the custom map in order to write to them. See Attention below.
Fixed
Fixed
Address
Register
(hex)
(decimal)
1DF0
7665
1DF1
7666
1DF2
7667
1DF3
7668
1DF4
7669
1DF5
7670
1DF6
7671
ATTENTION
Time registers must all be written in a single transaction. Writing to Week Day is optional.
56
18
C0
00
18
C0
00
08
42
C8
00
08
42
C8
00

Table 6-6 Time parameters

Parameter
Hours
Minutes
Seconds
Month
Day
Year
Week Day
HC900 Process Controller Communications User Guide
04
04
CRC
CRC
00
42
5D
00
42
5D
Access
Notes
R/W
0 to 23
R/W
0 to 60
R/W
0 to 60
R/W
1 to 12
R/W
1 to 31
R/W
1970 to 2037
The values read are always in the range
of 1970 to 2037 for a write. 0 – 37
represents 2000 – 2037, 70 – 99
represents 1970 – 1999
R
0 to 6 (0 = Sunday)
47
AE
47
AE
CRC
CRC
Revision 13
April 2017