Object
Identifier
Name
8001
kVA System Net
8010
kVA L1
8020
kVA L2
8030
kVA L3
8040
kVA Demand System Max
8050
kVA Demand System Now
9000
Displacement PF System
9030
Apparent PF System
9060
Displacement PF L1
9090
Displacement PF L2
9120
Displacement PF L3
9150
Apparent PF L1
9180
Apparent PF L2
9210
Apparent PF L3
10000
Measured Line Frequency
10010
Time Since Reset
DENT
Instruments
PowerScout 24
All Things BACnet
Description
* System=sum of three phases
System Net Apparent Power (kVA). Signed net value of (kVA L1) +
(kVA L2) + (kVA L3)
Individual Phase Apparent Powers (kVA) (signed)
Sign is set to the sign of the kW
"
System Maximum Instantaneous kVA Demand (kVA, resettable). It
displays the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset the value is not reset but
it does not update again until 1 demand window elapses.
(Unsigned/Absolute)
Average kVA for most recent demand window (resettable). Displays
the default value after a CAM or reset, or power cycle. Updates
every min thereafter. True demand value takes a demand period to
get to actual value. (Unsigned/Absolute)
System Total Power Factor (PF) (Signed)
System Total Power Factor (PF) (Signed)
Individual Phase displacement Power Factor (PF)
"
"
Individual Phase apparent Power Factors (PF)
"
"
Line Frequency (Hz)
Seconds since accumulator registers were reset.