DENT Instruments PowerScout 24 Operator's Manual page 87

Power meter and viewpoint software
Hide thumbs Also See for PowerScout 24:
Table of Contents

Advertisement

Object
Identifier
Name
3040
Volts L1 to L3
3050
Volts L1 to Neutral
3060
Volts L2 to Neutral
3070
Volts L3 to Neutral
4010
Amps System Average
4020
Amps L1
4030
Amps L2
4040
Amps L3
5000
kVAR System
5001
kVAR System Net
5030
kVAR L1
5060
kVAR L2
5090
kVAR L3
5120
kVAR Demand System Max
5130
kVAR Demand System Now
6010
kVARh System
7000
kVAh System Total
8000
kVA System
DENT
Instruments
PowerScout 24
All Things BACnet
Description
* System=sum of three phases
"
Individual Phase to Neutral Voltages (V)
"
"
Average of all phases.
Individual Phase Currents (A)
"
"
System Total Reactive Power (kVAR). Unsigned absolute (ABS) value
of ABS (kVAR L1) + ABS (kVAR L2) + ABS (kVAR L3)
System Total Reactive Power (kVAR). Signed net value of (kVAR L1)
+ (kVAR L2) + (kVAR L3)
Individual Phase Reactive Energy LSW (kVARh) (Signed)
"
"
System Maximum Instantaneous kVAR Demand (kVA, resettable). It
displays the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset the value is not reset but
it does not update again until 1 demand window elapses.
(Unsigned/Absolute)
Average kVAR demand for most recent window (resettable).
Displays the default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value takes a demand
period to get to actual value. (Unsigned/Absolute)
System Total Reactive Energy (Unsigned/Absolute)
System Total Apparent Energy (Unsigned/Absolute)
System Total Apparent Power (kVA). Unsigned absolute (ABS) value
of ABS (kVA L1) + ABS (kVA L2) + ABS (kVA L3)
87