DENT Instruments PowerScout 24 Operator's Manual page 71

Power meter and viewpoint software
Hide thumbs Also See for PowerScout 24:
Table of Contents

Advertisement

Modbus
Offset
Register
46053
6052
Positive Apparent PF L1
46054
6053
Positive Apparent PF L2
46055
6054
Positive Apparent PF L3
46056
6055
Amps L1
46057
6056
Amps L2
46058
6057
Amps L3
46059
6058
Volts L1 to Neutral
46060
6059
Volts L2 to Neutral
46061
6060
Volts L3 to Neutral
46062
6061
Time Since Reset LSW (Seconds)
46063
6062
Time Since Reset MSW
(Seconds)
46080
6079
Positive kW System Average
46081
6080
kW Demand System Minimum
46082
6081
kVA Demand System Maximum
46083
6082
kVA Demand System Now
46084
6083
kVAR Demand System Max
DENT
Instruments
PowerScout 24
All Things Modbus
Description
* System=sum of three phases
Individual Phase Positive Apparent Power Factors
(aPF); Register is 100x actual value (If the Individual
aPF(44053) is positive, this register will contain that
value else it will be zero)
"
"
Individual Phase Instantaneous Currents (A)
"
"
Individual Instantaneous Phase to Neutral Voltages
(V)
"
"
Seconds since kWh, kVAh, kVARh and associated
Demand registers were reset. LSW (resettable)
Seconds since CAM. MSW
Equals Positive KWH_SYSTEM_L&M ÷
(TimeSinceReset_L&M seconds /3600 seconds/Hr)
(resettable)
Min Average power window (kW)
Maximum Instantaneous kVA Demand (kW,
resettable).
System Average kVA Demand for the most recent
(current) Demand Window (resettable).
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.
71