DENT Instruments PowerScout 24 Operator's Manual page 66

Power meter and viewpoint software
Hide thumbs Also See for PowerScout 24:
Table of Contents

Advertisement

Modbus
Offset
Register
44040
4039
kVAR L3
44041
4040
kVAh L1 LSW
44042
4041
kVAh L1 MSW
44043
4042
kVAh L2 LSW
44044
4043
kVAh L2 MSW
44045
4044
kVAh L3 LSW
44046
4045
kVAh L3 MSW
44047
4046
kVA L1
44048
4047
kVA L2
44049
4048
kVA L3
44050
4049
Displacement PF L1
44051
4050
Displacement PF L2
44052
4051
Displacement PF L3
44053
4052
Apparent PF L1
44054
4053
Apparent PF L2
44055
4054
Apparent PF L3
44056
4055
Amps L1
44057
4056
Amps L2
44058
4057
Amps L3
44059
4058
Volts L1 to Neutral
44060
4059
Volts L2 to Neutral
44061
4060
Volts L3 to Neutral
44062
4061
Time Since Reset LSW
DENT
Instruments
PowerScout 24
All Things Modbus
Description
* System=sum of three phases
"
Individual Phase Apparent Energy LSW (kVAh)
Individual Phase Apparent Energy MSW (kVAh)
"
"
"
"
Individual Phase Apparent Powers (kVA)
"
"
Individual Phase displacement Power Factor (PF)
"
"
Individual Phase apparent Power Factors (PF)
"
"
Individual Phase Currents (A)
"
"
Individual Phase to Neutral Voltages (V)
"
"
Seconds since KWH register was reset. LSW