Download Print this page

AEMC MN03 User Manual

Ac current probe

Advertisement

Quick Links

AC Current Probe
Model MN03
User Manual
DESCRIPTION
The MN03 (Cat. #2129.18) is small, compact AC current probe. Designed to meet the most stringent
demands in industry and electrical contracting, they also meet the latest safety and performance
standards. The probe has a measurement range up to 100Arms which makes it a perfect tool for
measurement with DMMs, recorders. The Model MN03 is compatible with any voltmeter, multimeter, or
other current measurement instrument with an input impedance greater than 1MΩ. To achieve the
stated accuracy, use the probe with a voltmeter having an accuracy of 0.75% or better.
WARNING
These safety warnings are provided to ensure the safety of personnel and proper operation of the
instrument.
• Read the instruction manual completely and follow all the safety information before attempting
to use or service this instrument.
• Use caution on any circuit: Potentially high voltages and currents may be present and may
pose a shock hazard.
• Read the Safety Specifications section prior to using the current probe. Never exceed the
maximum voltage ratings given.
• Safety is the responsibility of the operator.
• ALWAYS connect the current probe to the display device before clamping the probe onto the
sample being tested.
• ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use.
Replace any defective parts immediately.
• NEVER use the current probe on electrical conductors rated above 600V in overvoltage
category III (CAT III). Use extreme caution when clamping around bare conductors or bus bars.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the current probe is protected by double or reinforced insulation. Use
only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before
using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from
HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES
Cat. I:
For measurements on circuits not directly connected to the AC supply wall outlet such as
protected secondaries, signal level, and limited energy circuits.
Cat. II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
Cat. III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
Cat. IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
RECEIVING YOUR SHIPMENT:
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately
with the carrier and notify your distributor at once, giving a detailed description of any damage.
Shop for AEMC products online at:
DataLoggerStore
www.
1.877.766.5412
.com

Advertisement

loading

Summary of Contents for AEMC MN03

  • Page 1 User Manual DESCRIPTION The MN03 (Cat. #2129.18) is small, compact AC current probe. Designed to meet the most stringent demands in industry and electrical contracting, they also meet the latest safety and performance standards. The probe has a measurement range up to 100Arms which makes it a perfect tool for measurement with DMMs, recorders.
  • Page 2: Electrical Specifications

    1%, no DC component, no external current Influence of Conductor Position in Jaw: carrying conductor, test sample centered. Load impedance Ω 0.1% of mV output @ 50/60Hz DataLoggerStore 1.877.766.5412 www. .com Shop for AEMC products online at:...
  • Page 3: Safety Specifications

    Storage Temperature: -40° to 176°F (-40° to +80°C) ORDERING INFORMATION Maximum Cable Diameter: AC Current Probe MN03 ....Cat. #2129.18 One Ø 0.39” (10mm) Includes a user manual and a product warranty Case Protection: and registration card.
  • Page 4 Please make sure that you have already read and fully understand the WARNING section on page 1. Making Measurements with the AC Current Probe Model MN03 • Connect the black lead of the current probe to “common” and the red lead to the AC voltage input on your DMM or other current measuring instrument.

This manual is also suitable for: