Micro ARE-M Series 24V Chargers, Single Phase
Operational Notes
1.
Load sharing is not intended to be effective below 10% of rated output. Operation below 10% may
result in unequal outputs or loss of output current form one of the units. It is recommended that where
paralleled units are being used to float a battery before the system load is installed, only one unit be
left operating.
2. Minor changes in the displayed output current may occur when paralleled units are operated at light
loads. This is an indication of the transfer of small currents between units and does not show up at
the load.
3.
It is possible for hunting to occur if the output voltages are misadjusted. Repeat step A under
"Adjustment".