Unipower ARE-M02406 Product Manual page 47

Micro are–m series 24v float chargers single-phase input
Table of Contents

Advertisement

Micro ARE-M Series 24V Chargers, Single Phase
8. When all setup parameters have been set, press ESC to return to the higher level menu
9. As needed, repeat the above for each of the three setup select screens in this section.
10. When parameters have been set, press ESC to return to the higher level menu or press ESC until the
Home screen appears.
4.3.4.2 Battery Temperature Compensation
Temperature compensation option 2 must installed for compensation to function. See Table 1-1 Model
Designation for the option location in the charger model number.
To enable compensation:
1. From the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the System Setpoints screen, press UP or DN until the Temperature Compensation screen
appears.
3. Press SEL. If the Battery Temperature Compensation Screen appears, go to step 5. If the Enter
Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password appears and then press SEL. Go to step
5.
5. At the Compensation disabled screen, press SEL. The equals sign (=) will begin to flash.
6. Press UP to toggle to "enable." Press one of the following:
Press SEL to store the change. The equals sign (=) will stop flashing. Go to step 7.
Press ESC to cancel or abort compensation. Go to step 10.
7. Press DN to display the Set Temperature Coefficient screen.
8. To change the coefficient, press SEL. The equals sign (=) will flash.
9. Press UP or DN to display the desired mv/Cell/C value. Press SEL to store the new value.
10. Press ESC to return to the Temperature Compensation screen. Either press UP or DN to move to
another Setup Select Screen or press ESC until the Home screen appears.
Note: Refer to the battery manufacturer for the correct temperature compensation value.
To disable Temperature Compensation:
1. From the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the System Setpoints screen, press UP or DN until the Temperature Compensation screen
appears.
3. Press SEL. If the Battery Temperature Compensation Screen appears, go to step 5. If the Enter
Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password appears and then press SEL. Go to step
5.
5. At the Compensation enabled screen, press SEL. The equals sign (=) will begin to flash. Press one
of the following:
Press UP to toggle to "disable." Press SEL to store the change. The equals sign (=) will stop
flashing.
Press ESC for Compensation to remain enabled and return to the higher level screen.
4-12
Setup and Operation
PM990-1070-24, Issue 12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Are-m02425Are-m02450Are-m02412Are-m024100

Table of Contents