ABB RED615 Product Manual page 14

Line differential protection and control
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Line Differential Protection and Control
RED615
Product version: 1.1
Degree of protection of flush-mounted IED
Front side
Rear side, connection terminals
Environmental conditions and tests
Environmental conditions
Operating temperature range
Short-time service temperature range
Relative humidity
Atmospheric pressure
Altitude
Transport and storage temperature range
Environmental tests
Dry heat test (humidity <50%)
Cold test
Damp heat test, cyclic
Storage test
Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
1 MHz burst disturbance test, class III:
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
1
1MRS756500 A
IP 54
IP 20
-25...+55ºC (continuous)
-40...+70ºC (<16h)
Note: Degradation in MTBF
and HMI performance out-
side the temperature range of
-25...+55ºC
<93%, non-condensing
86...106 kPa
up to 2000 m
-40...+85ºC
According to IEC 60068-2-2
Test values:
• 96 h at +55ºC
• 16 h at +85ºC
According to IEC 60068-2-1
Test values:
• 96 h at -25ºC
• 16 h at -40ºC
According to IEC 60068-2-30
Test values:
• 6 cycles at +25...55°C,
humidity 93...95%
According to IEC 60068-2-48
Test values:
• 96 h at -40ºC
• 96 h at +85ºC
According to IEC 61000-4-18
and IEC 60255-22-1, level 3
2.5 kV
1.0 kV
According to IEC 61000-4-2,
IEC 60255-22-2, level 3
6 kV
8 kV
ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents