Vacon NX series User Manual page 79

Active front end unit (afe) air cooled
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

Installation
5.4.3.2
Control terminals on OPTA1
Here you see the basic description of the terminals of the I/O board and the relay board. For more
information, see Jumper selections on the OPTA1 basic board. For more information on control
®
terminals, see VACON
Reference potentiometer,
1-10kΩ
*) See Fig. 26 Jumper blocks on OPTA1.
Parameter references for I/O on keypad and NCDrive are: An.IN:A.1, An.IN:A.2, DigIN:A.1, DigIN:A.2,
DigIN:A.3, DigIN:A.4, DigIN:A.5, DigIN:A.6, AnOUT:A.1 and DigOUT:A.1.
To use the control voltage output +24V/EXT+24V:
• you can wire the +24V control voltage to digital inputs through an external switch.
• you can use the control voltage to power up external equipment, such as encoders and
auxiliary relays.
Note that the specified total load on all available +24V/EXT+24V output terminals must not exceed
250mA. The maximum load on the +24V/EXT+24V output per board is 150mA.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
All in One Application manual.
Terminal
Reference voltage
1
+10V
ref
Analogue input,
AI1+
2
voltage or current
GND/AI1-
3
Analogue input common
Analogue input,
4
AI2+
voltage or current
5
GND/AI2-
Analogue input common
6
24 V aux. voltage
+24V
GND
7
I/O ground
DIN1
Digital input 1
8
DIN2
Digital input 2
9
DIN3
10
Digital input 3
CMA
11
Common A for DIN1—DIN3
+24V
12
Control voltage output
GND
13
I/O ground
14
DIN4
Digital input 4
15
DIN5
Digital input 5
16
DIN6
Digital input 6
17
CMB
Common B for DIN4-DIN6
18
AO1+
Analogue signal (+output)
19
AO1-
Analogue output common
20
DO1
Open collector output
Figure 48. The control terminal signals in OPTA1
Standard I/O board
Signal
Description
Maximum current 10 mA
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
±15%, max. 250 mA (all boards total)
150 mA (from single board)
Can also be used as external power backup for
the control unit (and fieldbus)
Ground for reference and controls
Ri = min. 5 kΩ
18-30 V = 1
Digital inputs can be disconnected from ground (*)
Same as terminal #6
Same as terminal #7
Ri = min. 5 kΩ
18-30 V = 1
Must be connected to GND or 24 V of I/O term.
or to ext.24 V or GND
Selection with jumper block X3 (*)
Output signal range: Current 0(4)-20 mA,
RL max 500 Ω or
Voltage 0-10 V, RL >1kΩ
Selection with jumper block X6 (*)
Maximum Uin = 48 VDC
Maximum current = 50 mA
vacon • 77