When E1-03 is set to F (User-defined V/f pattern), you can set the parameters E1-04 to E1-10. If E1-03
is set to anything other than F, you can only read parameters E1-04 to E1-10. If the V/f characteristics
INFO
are linear, set E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
Output voltage (V)
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points:
When changing control method, the parameters E1-07 to E1-10 will change to the factory settings for that
control method.
Be sure to set the four frequencies as follows:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
Fig 6.54 User-Set V/f Pattern
Frequency (Hz)