Overall Switchgear; Padlocks And Keylocks; Circuit Breaker Racking Port Padlock Provision; Figure 9-6: Ct Wires Connected - GE SecoGear Installation, Operation And Maintenance Manual

5kv-15kv ieee metal-clad switchgear
Hide thumbs Also See for SecoGear:
Table of Contents

Advertisement

2. Route and retain CT wires through the upper channels of the
front of gear and connect to the Short Circuiting Terminal
Blocks (Figure 9-6).
Figure 9-6: Shorting Terminal Blocks
3. Verify that the shutter operation (Figure 9-7) does not
interfere with CTs or wire routings. Finally, tie the wire to
the vertical support.

Figure 9-7: CT Installed, Shutters in Open Position

Overall Switchgear

Make the following checks on the complete switchgear
equipment.
1. Clean and inspect all painted surfaces, and retouch
where necessary.
2. Check to see that all anchor bolts and other structural
bolts are tight.
3. Check that all circuit breaker and instrument compartment
door latches operate properly.
4. If the switchgear is equipped with heaters, check to see that
all heaters are energized and operating.
5. For exterior vent openings in equipment furnished with
air filters, the foam filter elements should be removed and
washed in warm soapy water, rinsed, and reassembled
at least annually. Elements should be inspected before
re-assembly and replaced if any signs of deterioration
are evident.

Padlocks and Keylocks

SecoGear offers various padlocking features and optional
keylock operation. In some cases, it is necessary to use
more than one padlocking feature for proper lockout/tagout
protection.

Circuit Breaker Racking Port Padlock Provision

The racking access port padlocking provision is located at the
bottom and in the middle of the door (Figure 9-8).

Figure 9-8: SecoGear Manual Racking Port Padlocked

This lock prevents racking in a circuit breaker whenever the
door is closed. The door padlocking provision, described
below, must also be used to make sure the circuit breaker
cannot be racked in by unauthorized personnel.
SecoGear – Installation, Operation and Maintenance Manual 50 of 56

Advertisement

Table of Contents
loading

Table of Contents