Figure 5-19: Rotate Interlock Pin Counterclockwise To Unlock The Latch Handle; Figure 5-20: Interlock Latch Handle; Figure 5-21: Stop In Proper Position; Figure 5-22: Eliminating Stop Interference - GE SecoGear Installation, Operation And Maintenance Manual

5kv-15kv ieee metal-clad switchgear
Hide thumbs Also See for SecoGear:
Table of Contents

Advertisement

1.
Once the VCB is in the switchgear compartment,
disengage the lift truck compartment interlock by rotating
the interlock pin counterclockwise, Figure 5-19, then
move the handle to the left and pull the latch handle
toward you and from the switchgear compartment until it
is fully retracted, Figure 5-20.
Figure 5-19. Rotate Interlock Pin Counterclockwise to Unlock the Latch Handle
Figure 5-20. Interlock Latch Handle
CAUTION
Verify that the VCB safety stop in the switchgear
compartment has returned to the normal
extended position.
2.
Verify that the VCB safety stop has returned to the
extended position, Figure 5-21. If necessary, release
by inserting a screw driver into the slot to dislodge,
Figure 5-22.
Figure 5-21. Stop in Proper Position
Figure 5-22. Eliminating Stop Interference
3.
Release the lift truck floor lock by depressing the lever on
the right or left-hand side of the floor lock and move the
lift truck away from the switchgear, Figure 5-23.
Figure 5-23. Release Floor Lock
SecoGear – Installation, Operation and Maintenance Manual 40 of 56

Advertisement

Table of Contents
loading

Table of Contents