Connecting A Pendant Float To The Alertmaxx2 Unit - Delta Membranes AlertMaxx2 Installation & Operating Manual

Foul water, pump station high level alarm
Table of Contents

Advertisement

AlertMaxx2

12.0 Connecting a pendant float to the AlertMaxx2 unit

1.
Using a draw cord, pull the float cable through the cable duct on the chamber.
2.
Insert a large cable gland into the far left hole of the AlertMaxx2 unit.
3.
Pull the float cable through the large cable gland on the AlertMaxx2 unit.
4.
Connect the black and blue cables from the float switch cable to the terminal strip (figure 6).
The brown cable should be disregarded and isolated to avoid possible shorting.
If the cable supplied with the float switch is too short, the cable can be extended using a cable with a
Only the first two (far left) inputs on the float terminal block are used - Blue & Black
10
PLEASE NOTE
minimum core cross sectional area of 1mm².
PLEASE NOTE
Figure 6. Wiring a pendant float switch