Standard Input/Output Expansion Module - Wieland Samos PRO COMPACT Manual

Hide thumbs Also See for Samos PRO COMPACT:
Table of Contents

Advertisement

12.3.4

Standard input/output expansion module

1126553227
Table 59: SP-DIO data sheet
Protection class
Protection type
Ambient temperature during opera-
tion
Storage temperature
Humidity
Fatigue strength
Shock resistance
• Continuous shock
• Brief shock
Electromagnetic compatibility
Power consumption via the internal
safety bus
Data interface
Plug-in terminal blocks and
connection data
Single-wire or fine-strand
Fine-strand with ferrules
Conductor size AWG
(use copper cables only)
Maximum tightening torque
Stripping length
Dimensions (W × H × L)
Weight
Power supply (A1, A2)
Supply voltage
Type of supply voltage
Power consumption
Switch-on time
Short-circuit protective device
Input circuit (I1–I4 & IY5-IY8)
Number of inputs
Input voltage HIGH
Input voltage LOW
Input current HIGH
Input current LOW
Wieland Electric GmbH | BA000966 | 08/2017 [8151]
SP-DIO
III (EN 61140)
Terminals: IP 20 (EN 60529)
Housing: IP 40 (EN 60529)
-25 ... +55 °C
-40 ... +70 °C
10 ... 95%, non-condensing
5 ... 150 Hz (EN 60068-2-6)
10 g, 16 ms (EN 60068-2-29)
30 g, 11 ms (EN 60068-2-27)
EN 61000 6 2, Class A (EN 55011) Emission
EN 61000-6-4 Immission
max. 0.5 W
Internal safety bus
Screw terminal
2
1 x 0.2–2.5 mm
2 x 0.2-1.0 mm
2
1 × 0.25-2.5 mm²
2 × 0.25–1.0 mm²
26-14
0.5-0.6 Nm (5-7 lbf-in)
7 mm
22.5 × 96.5 × 121 mm
150 g (± 5%)
24 V DC (16.8 to 30 V DC)
PELV or SELV
max. 120 W (depending on load)
max. 18 s
4 A gG (tripping characteristic B or C)
4 to max. 8 (depending on configuration)
13 V DC... 30 V DC
–3 V DC ... +5 V DC
2 mA ... 3.5 mA
0 mA... 1.0 mA
Technical data
Spring-loaded terminal
2
2 x 0.2-1.5 mm
2 × 0.25-1.5 mm²
24-16
22.5 × 107 × 121 mm
150 g (± 5%)
95