Connection Of Multiple Safety Mats/Bumpers; Mode Selection Switch - Wieland Samos PRO COMPACT Manual

Hide thumbs Also See for Samos PRO COMPACT:
Table of Contents

Advertisement

4.1.7

Connection of multiple safety mats/bumpers

888461963
When multiple safety mats/bumpers are used to improve diagnosis, it may be wise to decouple
the test pulse outputs.
4.1.8

Mode selection switch

888464651
Electrical connection: Example from samosPLAN  6
Operating mode selection
switch (1 from 2) to 24 V
Operating mode selection
switch (1 from 2) to test
output
Function
Testing
NOTICE
• Operating mode selection switches without test pulses enable 2 to 8 operating modes;
operating mode selection switches with test pulses enable 2 to 4 operating modes.
• When wiring the tested operating mode selection switches, note that when using an odd-
numbered test output (e.g. T1, T3 ... or X1, X3 ...), odd-numbered inputs (e.g. I1, I3, I5 ...)
must be used; when using an even-numbered test output (e.g. T2, T4 ... or X2, X4 ...),
even-numbered inputs (e.g. I2, I4, I6 ...) must also be used.
• You can find additional information in the operating instructions for the operating mode
selection switches.
Wieland Electric GmbH | BA000966 | 08/2017 [8151]
Info
Possible
Connecting devices
Channel 1: Contact
between 24 V and I1
Channel 2: Contact
between 24 V and I2
Channel 1: Contact
between T1 and I3
Channel 2: Contact
between T2 and I4