Siemens SIMATIC S7-1500 Manual page 20

Digital output module dq 16x24vdc/0.5a ba (6es7522-1bh10-0aa0)
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Diagnostics alarms
5.1 Status and error displays
Meaning of the LED displays
The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1
RUN/ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
Flashes
Flashes
LED PWR1/PWR2
Table 5- 2
PWR1/PWR2 status display
LED PWRx
Off
On
LED CHx
Table 5- 3
CHx status display
LED CHx
Off
On
20
Meaning
Voltage missing or too low at backplane bus.
Module is starting up.
Module is ready.
Hardware defective.
Meaning
Supply voltage L+ too low or missing.
Supply voltage L+ is present and OK.
Meaning
0 = Status of the output signal.
1 = Status of the output signal.
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
Check the L+ supply voltage.
---
---
---
Digital output module DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0)
Remedy
Remedy
Remedy
Manual, 09/2016, A5E32364017-AC

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents