Connection Diagrams - Siemens SQS35.53 Manual

Sqs35 series, sqs65 series, sqs85 series, electric actuators for valves with a 5.5 mm stroke
Table of Contents

Advertisement

Connection
diagrams
Note
SQS65, SQS65.5
(AC 24 V, DC 0 ...10 V)
SQS65.2
(AC 24 V, DC 2 ...10 V)
Siemens Building Technologies
Landis & Staefa Division
Connection terminals
SQS65....
G
Y
R
M
U
G0
All connection options are illustrated in the connection diagrams. How many and which
of these are used, depends on the system.
If a device is connected to terminal R, the factory-fitted bridge across R – M on the
printed circuit board must be cut through.
SP
Y
R
M
(1,2,3)
N1
R1
G
Y(Y')
R
M
GO
SN
SP
LS
NS
Y (1,3)
G
Y
R
G0
SN
Equipment
F1
Frost detector
K1
On/off switch
N1
CLASSIC controller
P1
Position indicator
R1
Position transmitter
G, G0
Operating voltage AC 24 V
G
System potential (SP) corresponds to LS on SQS65.2
G0 System neutral (SN) corresponds to NS on SQS65.2
Signal inputs
Y
SQS65, SQS65.5
SQS65.2
RSQS65, SQS65.2, SQS65.50 ...1000 ohms
M
Measuring neutral
USignal output
SQS65, SQS65.2, SQS65.5
G
R
M
Y
G0
F1
P1
U
Y1
R
M
R
N1
R1
M
K1
On/off switch
N1CLASSIC controller
P1Position indicator
R1Position transmitter
Y1Actuator
DC 0...10 V
DC 2...10 V
DC 0...10 V
K1
G
M
Y
G0
F1
P1
U
Y1
CM1N4573E / 06.2001
K1
7/8