Approved Flue System; Installation Precautions - Lochinvar ECOKNIGHT EKW46CE Installation Manual

Floor standing gas fired condensing circulating type water heater
Table of Contents

Advertisement

10.5

APPROVED FLUE SYSTEM

For Concentric and Twin pipe flue systems only the Lochinvar supplied M&G flue system must be used
The approved flue system is not suitable for use external to the building. If external routes cannot be
avoided, a flue system manufacturer should be consulted to supply a suitable alternative.
10.6

INSTALLATION PRECAUTIONS

The approved flue system is rated to 120C max. To prevent the exhaust temperature exceeding this, the appliance is
supplied with a flue gas temperature sensor.
This must be fitted during the installation of the flue system. Failure to do so may lead to severe
personal injury, death or substantial property damage.
The water heater must not be operated unless the complete flue system is installed. This includes the water heater
connections, concentric adaptor (if required) flue pipes, air ducts (if required) and terminals. If discharging at low level, a
suitable flue guard must be installed.
During assembly precaution should be taken to ensure that the internal sealing ring is seated correctly.
Due to the close tolerances in the flue system, it may be necessary to use a twisting action to fit the joints together. No
lubrication other than water should be used.
18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents