Connecting The Machine For A Specific Direction Of Rotation; Terminal Box - Siemens SIMOTICS XP 1MD4 Operating Instructions And Installation Instructions

Induction motor
Table of Contents

Advertisement

Electrical connection
6.2 Connecting
1
6.2.6

Connecting the machine for a specific direction of rotation

If the machine has one shaft extension or two shaft extensions with different diameters, the
direction of rotation when looking at the front of the single or the thicker shaft extension is
defined as follows:
● If you are connecting power supply cords with a phase sequence of L1, L2, L3 at U, V, W,
● If you transpose two connections, e.g. L1, L2, L3 at V, U, W, the resulting rotation will be
Machines which must run only in one specific direction of rotation are marked with a direction
of rotation arrow.
6.2.7

Terminal box

● The number and size of the cable entry tapped holes can be found in the machine dimension
● Only use cable entries that are suitable for the cable.
● Only use suitable cable entries and cables for the prevailing ambient temperature.
● Check the cable glands and cables to ensure that they are correctly sealed and firmly
● Correctly close and seal threads or holes that are not being used ensuring that the IP degree
Please note the following points for explosion-protected machines:
● Replace the cable glands that are not being used by appropriately certified screw plugs.
● If you are using cable glands, use only appropriately certified cable glands with strain relief.
Note
Undrilled entry plate
If the entry plate is undrilled, you should match the number and size of the cable glands to the
operating conditions. Not applicable for terminal boxes of the Ex d type of protection.
54
U
1
-
1 Designation
x
Index for winding start (1) or end (2) or if there is more than one connection per
winding
x Additional indices for cases in which it is obligatory to connect parallel power feed
cables to several terminals with otherwise identical designations
the resulting rotation will be clockwise.
counter-clockwise.
drawing.
seated.
of protection is maintained. The IP degree of protection is specified on the rating plate.
Comply with the installation and operation conditions specified in the certificate for these
cable glands and check that they have been fully complied with.
SIMOTICS XP 1MD4/1MD5
Operating Instructions 05/2015