Manual Configuration Of Central Account Management - ABB RELION 670 SERIES Manual

Cyber security deployment guideline
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 511 399-UEN B
5.3.1
670 series 2.2 IEC
Cyber security deployment guideline
If the Central Account Management activation fails, the activate parameter will be
reset and Central Account Management must be activated again and a failure
message will be indicated in PCM Output window.
When Central Account Management is activated, any ongoing sessions with the
IED will continue until they are closed.

Manual configuration of Central Account Management

It is possible to edit Central Account Management configuration parameters and
modify them (if needed) in PCM600. In order to edit configuration parameters,
right click on the Device and select Edit as shown below.
IEC15000288 V1 EN-US
Figure 49:
Edit configuration
The following screen appears, where in which user can edit the Central Account
Management configuration parameters and/or manually change the certificate.
IEC15000289 V1 EN-US
Figure 50:
Local configuration
Central Account Management
GUID-D4123E80-3D91-4767-9B67-5936CF1030D5 v1
Section 5
59