Descriptions Of Led Functions - Delta CP2000 Series User Manual

Delta fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

Key
Direction: Left / Right / Up / Down
1.
2.
Function Key
1.
2.
HAND ON Key
1.
2.
3.
1.
2.
3.

Descriptions of LED Functions

LED
Steady ON: operation indicator of the AC motor drive, including DC brake, zero speed,
Blinking: drive is decelerating to stop or in the status of base block.
Steady OFF: drive doesn't execute the operation command
Steady ON: stop indicator of the AC motor drive.
Blinking: drive is in the standby status.
Steady OFF: drive doesn't execute "STOP" command.
Operation Direction LED
1. Green light is on: the drive is running forward.
2. Red light is on: the drive is running backward.
3. Twinkling light: the drive is changing direction.
Operation Direction LED under Torque Mode
1. Green light is on, when torque command is greater than or equal to zero, and the drive is
2. Red light is on, when the torque command is smaller than zero, and the drive is running
3. Twinkling light: when the torque command is smaller than zero, and the drive is running
(Only KPC-CE01 support this function)
Steady On: In HAND/LOC mode
Steady Off: In AUTO/REM mode
(Only KPC-CE01Support this function )
Steady On: In AUTO/REM mode
Steady Off: In HAND/LOC mode
In the numeric value setting mode, it is used to move the cursor and change the numeric
value.
In the menu/text selection mode, it is used for item selection.
The function keys are default settings from the factory, and can be defined by users. The
factory settings of F1 and F4 work with the function list below. For example, F1 is JOG
function, F4 is a speed-setting key for adding/deleting user defined parameters.
Other functions must be defined by TPEditor first (please use version 1.40 or above).
TPEditor software can be downloaded at:
http://www.deltaww.com/services/DownloadCenter2.aspx?secID=8&pid=2&tid=0&CID=06&itemID=060302&typeID=1&downloadID=,&title=-- Select
Product Series --& atatype=8;&check=1&hl=en-US
Please refer to instruction for TPEditor in Chapter 10-3.
This key is executed by the parameter settings of the source of Hand frequency and hand
operation. The factory settings of both source of Hand frequency and hand operation are
the digital keypad.
Press HAND ON key at stop status, the setting will switch to hand frequency source and
hand operation source. Press HAND ON key at operation status, it stops the AC motor
drive first (display AHSP warning), and switch to hand frequency source and hand
operation source.
Successful mode switching for KPC-CE01, "HAND" LED will be on; for KPC-CC01, it will
display HAND mode on the screen.
This key is executed by the parameter settings of the source of AUTO frequency and
AUTO operation. The factory setting is the external terminal (source of operation is
4-20mA).
Press Auto key at stop status, the setting will switch to auto frequency source and auto
operation source. Press Auto key at operation status, it stops the AC motor drive first
(display AHSP warning), and switch to auto frequency source and auto operation source.
Successful mode switching for KPC-CE01, "AUTO" LED will be on; for KPC-CC01, it will
display AUTO mode on the screen
standby, restart after fault and speed search.
running forward.
backward.
forward.
Chapter 7 Optional AccessoriesCP2000
Descriptions
Descriptions