Wiring of COM Port

2.2.2 Applicable Cable

The following cables should be used.
 Suitable wires (strand wire): RS-485 communication wire
Classifi-
Cross-sectional
cation
view
Shielded
Shield
twisted
Conductor
pair
VCTF
Conductor
Use shielded twisted pair cables.
Use only one type of transmission cable. Do not mix more than 1 type.
Twisted pair cables are recommended in noisy environments.
For RS-485 transmission line, use crossover wiring, and ground one end of
a shielded cable.
If two wires are connected to the plus and minus terminals of RS-485, use
wires of the same material and the same cross-sectional area between 0.5
and 0.75 mm
2-4
Conductor
Size
Resist-
ance
(at 20°C)
2
1.25 mm
Max.
(AWG16)
16.8Ω/km
Coating
or more
Insulator
2
0.5mm
Max.
(AWG20)
33.4Ω/km
or more
2
0.75mm
Coating
Max.
(AWG18)
Insulator
25.1Ω/km
or more
2
.
Insulator
Cable
Mate-
Thick-
diam.
rial
ness
Poly-
Max.
Approx.
ethylene
0.5 mm
8.5 mm
Poly-
Max.
Approx.
ethylene
0.5 mm
7.8mm
Polyviny
Max.
Approx.
lchloride
0.6mm
6.6mm
Sample appropriate
cable
Sumiden Hitachi Cable
2
KPEV-S1.25 mm
× 1P
Belden Inc. 9860
Sumiden Hitachi Cable
2
KPEV-S0.5 mm
× 1P
Belden Inc. 9207
2
VCTF0.75 mm
× 2C
(JIS)