4.2.3 Memory Block No. of Link Relays and Link Registers to be Used

• The memory areas of link relays and link registers are divided for PLC link 0 and for PLC link
1. Either area can be selected, and max. 1024 points (64 words) can be used for link relays,
and max. 128 words can be used for link registers.
• Specify "0" for using memory blocks in the first half, and "1" for using memory blocks in the
latter half.
Structure of a link area

4.2.4 Ranges of Link Relays and Link Registers to be Used

• Specify the ranges of memory areas of link relays and link registers to be actually used.
• Link relays and link registers that are not to be used for linking may be used in place of
internal relays and data registers.
Example) Setting of ranges for use (in the case of PLC link 0)
• The diagram below indicates a case when "50" (50 words from WL0 to WL49) is specified for
the range of link relay, and "100" (100 words from LD0 to LD99) for the range of link register
to be used.
• As the range to be used in PLC link 0, specify "64" (64 words) when all link relays are to be
used, and "128" (128 words) when all link registers are to be used.
4.2 Setting Items for PLC Link
4-5