Setting Alarm Setpoints

The following operating procedure describes an example of setting a value of 160.0 in the
alarm-1 setpoint parameter. Before setting the alarm setpoint, check the alarm type.
To change the alarm type, see "2.4 Changing Alarm Type."
Alarm output terminals
Alarm-1 (terminal numbers
Alarm-2 (terminal numbers
Alarm-3 (terminal numbers
Alarm-4 (terminal numbers
1.
Bring the operating display into view
(display appears at power on).
PV
SET/ENT
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu "OP.PA".
PV
SET/ENT
3.
Press the
key once to display the
SET/ENT
parameter "A1".
PV
SET/ENT
4.
Press the
or
required setpoint.
PV
SET/ENT
Factory-set defaults
-
)............PV high limit alarm
6
7
-
)............PV low limit alarm
5
7
-
)............PV high limit alarm
4
7
- -
).......PV low limit alarm
1
2
3
Displays PV.
AL1
2
3
4
Displays
menu "OP.PA".
AL1
2
3
4
Displays
parameter
"A1".
AL1
2
3
4
key to display the
AL1
2
3
4
Blinks during
change.
<3. Operations>
5.
Press the
SET/ENT
setpoint.
PV
SET/ENT
You can take the same steps for alarm-2
setpoint (A2), alarm-3 setpoint (A3), and
alarm-4 setpoint (A4) that are displayed
after this.
6.
Press the
SET/ENT
onds. This returns you to the display
shown at power-on (figure below).
PV
SET/ENT
IM 05F01D02-41E
key once to register the
AL1
2
3
4
key for more than 3 sec-
Displays PV.
AL1
2
3
4
1st Edition : May 31,2000-00
3-2