1.3

How to Connect Wires

1)
Before carrying out wiring, turn off the power to the indicator and check that the cables
to be connected are not alive with a tester or the like because there is a possibility of
electric shock.
CAUTION
2)
Wiring must be carried out by personnel who have basic electrical knowledge and
practical experience.
NOTE
1)
Provide power from a single-phase instrument power supply. If there is a lot of noise in
the power line, insert an insulating transformer into the primary side of the line and use
a line filter (recommended part: ZAC2205-00U from TDK) on the secondary side.
As a countermeasures against noise, do not place the primary and secondary power
cables close to each other.
2)
For thermocouple input, use shielded compensating lead wires for wiring. For RTD
input, use shielded wires that have low conductor resistance and cause no significant
differences in resistance between the three wires.
The cables to be used for wiring, terminal specifications, and recommended parts are
as shown below.
3)
Alarm output relays have a life of 100,000 times that of the resistance load, use
auxiliary relays to turn on/off a load.
4)
The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves
causes malfunction or relay failure; always insert a CR filter for use with alternating
current or a diode for use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
I For DC Relay Wiring
UM350/UM330
UM's contact
(Use one with a relay coil
rating less than the UM's
External DC power supply
Relay
R
Diode
(Mount it directly
to the relay coil
Relay
terminal (socket).)
contact rating.)
<1. Installation>
I For AC Relay Wiring
UM350/UM330
UM's contact
Relay
(Use one with a relay coil
rating less than the UM's
contact rating.)
IM 05F01D02-41E
1-5
External AC power supply
R
CR filter
(Mount it directly
to the relay coil
terminal (socket).)