Changing PV Input Type

The following operating procedure describes an example of changing the setting of K-type
thermocouple (-199.9 to 500.0 C) to RTD Pt100 (-199.9 to 500.0 C) and a measurement
range of 0.0 to 200.0 C.
PV input terminal
Thermocouple/mV/V input..............................
RTD input ..................................................
1.
Bring the operating display into view
(display appears at power on).
PV
SET/ENT
2.
Press the
key for more than 3 sec-
SET/ENT
onds to call up the menu "OP.PA".
PV
SET/ENT
3.
Press the
key once to display the
menu "STUP".
PV
SET/ENT
4.
Press the
SET/ENT
key once to display the
parameter "PWD".
PV
SET/ENT
-
12
13
- -
11
12
Displays PV.
AL1
2
3
4
Displays
menu "OP.PA".
AL1
2
3
4
Displays
menu "STUP".
AL1
2
3
4
Displays
parameter
"PWD".
AL1
2
3
4
<2. Initial Settings>
13
5.
Press the
SET/ENT
menu "FUNC".
6.
Press the
menu "I/O".
7.
Press the
SET/ENT
parameter "IN" (PV input type).
8.
Press the
required setpoint. The figure below shows
an example of changing to RTD Pt100
(-199.9 to 500.0 C).
key once to display the
Displays
menu "FUNC".
PV
AL1
2
3
4
SET/ENT
key once to display the
Displays
menu "I/O".
PV
AL1
2
3
4
SET/ENT
key once to display the
Displays
parameter
PV
"IN".
AL1
2
3
4
SET/ENT
or
key to display the
PV
Blinks during
change.
AL1
2
3
4
SET/ENT
IM 05F01D02-41E
1st Edition : May 31,2000-00
2-7