Lennox LGH180H Installation Instructions Manual page 55

13 ton, 15 ton, 17.5 ton, 20 ton, 25 ton rooftop packaged units
Hide thumbs Also See for LGH180H:
Table of Contents

Advertisement

TABLE 29
580731
Units With Automated Logic DDC (Target) Settings
Para­
Factory
Field
meter
Setting
Setting
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
91
120
Compressor minimum run time.
111
3
Thermostat with three cooling stages.
Damper "start open" CO
118
400
DCV.
Damper "full open" CO
119
2000
DCV.
139
74
Backup occupied cooling setpoint.
Time delay between heating and cooling
153
60
mode.
TABLE 30
580732
Units With Room Sensor, CPC/LSE Gateway Settings
Use menu SETUP > NETWORK INTEGRATION. Set "L CONNEC­
TION" and network address.
LCONN ADDRESS:
Factory Setting
Para-meter
156
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT
PARAMETERS
5200
12
CFM
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
5200
CFM
4675
CFM
3375
CFM
3375
CFM
5200
CFM
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
0%
50%
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
29
101%
219
70%
216
10%
220
10%
224
100
30
70%
Description
setpoint for
2
setpoint for
2
LGH/LCH 156H/180H/210H (3-Compressor) MSAV
180
210
6000
7000
CFM
CFM
6000
7000
CFM
CFM
5400
6300
CFM
CFM
3900
4550
CFM
CFM
3900
4550
CFM
CFM
6000
7000
CFM
CFM
0%
0%
0%
0%
50%
50%
101%
101%
70%
70%
10%
10%
10%
10%
100
100
70%
70%
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Para­
Factory
meter
Setting
105
6
Units With BACnet Module (Kohl's) Settings
Use menu SETUP > NETWORK INTEGRATION. Set "BACNET"
and network address.
BACNET MAC ADDRESS:
Parameter
Factory Setting
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
137
TABLE 33
580745
Field
Description
Setting
CFM Blower CFM during smoke detection.
Blower CFM during heating.
CFM
CFM
Blower CFM during compressor 3 operation.
CFM
Blower CFM during compressor 2 operation.
Blower CFM during compressor 1 operation.
CFM
Blower CFM during ventilation.
CFM
% Damper min. position during LOW blower operation.
% Damper min. position during HIGH blower operation.
% Min. damper % for stage 1 power exhaust operation.
Damper minimum position during G blower operation. (Setting parameter 29 to
%
Open
"101" disables parameter 29 and passes control to parameter 9 or 132)
% Min. damper % for stage 2 power exhaust operation.
% Deadband % for stage 1 power exhaust operation.
% Deadband % for stage 2 power exhaust operation.
Sec Stage 1 power exhaust off-delay in seconds.
%Speed Minimum blower speed % for stage 2 power exhaust operation.
Page 55
TABLE 31
580734
Units With Hot Gas Reheat
Field
Setting
Description
Hot Gas Reheat Option 6: Reheat is
only possible if blower is energized dur­
ing occupied periods. Controlled by RH
sensor (A91) connected to input
A55_P298_5 and set point set at para­
meter 106 (default 60%).
TABLE 32
580733
Setting
Sets the backup occu­
pied heating setpoint to
65
65F.
507124-04
Description
3/2016