Technical documentation
3.6.

Organisation of the software versions

The modules of the FMS are each operated with the current software version. The log file
"FMS3000_Software_ChangeLog.txt" lists the current status of the software (see document: 1.4
FMS_Software_Beschreibung).
3.7.

Sequence of on-board commissioning

Step 1. Connect all detectors and outputs.
Step 2. Check all wiring for earth connection, short circuit, polarity and interference voltages!
Step 3. Switch on the FMS and check the overall condition.
Step 4. Check the fire detector loops.
Step 5. Check the outputs and additional main panels or other peripheral devices.
4.

Maintenance

4.1.
Checking fire detectors
The functioning of fire detectors is to be checked at yearly intervals. Dirty and defective detectors are
to be replaced immediately. Defective of missing detectors cause a fault report.
4.2.

Checking and changing the accumulator

The average lifetime of the accumulator is about 4-5 years at an ambient temperature of 25°C. The
accumulators should therefore be replaced as a precaution every 4-5 years. In addition, the main
module monitors the accumulator. If the module detects that a fully charged accumulator is weak, then
the FMS shows a fault. In this case, the accumulator must be replaced before time!
The average lifetime of the lithium battery (type CR 2032) for the real time clock is about 10 years at
an ambient temperature of 25°C. After this period, it is to be replaced.
When changing the lithium battery, care should be taken that the main module is switched off, since
changing the battery can cause a short circuit. The data of the real time clock (date, time) must be re-
entered after changing the battery.