Installation and start-up of KEOR HPE UPS 200 kVA
Installazione e avviamento KEOR HPE UPS 200 kVA
INSTALLATION AND START-UP OF
INSTALLAZIONE E AVVIAMENTO UPS
Index / Indice
ENGLISH LANGUAGE .............................................................................. 8
1
SCOPE ............................................................................................. 10
2
SAFETY RULES AND WARNINGS ................................................. 11
2.1
USE OF THE UPS .................................................................................................... 11
2.2
UPS RATING PLATE ............................................................................................... 12
2.3
SPECIAL SAFETY WARNINGS ............................................................................... 13
2.3.1
General warnings ............................................................................................ 13
2.3.2
Personnel ......................................................................................................... 13
2.3.3
Transport and handling .................................................................................. 13
2.3.4
Installation ....................................................................................................... 14
2.3.5
Electrical connection ...................................................................................... 15
2.3.6
Operation ......................................................................................................... 16
2.3.7
Maintenance .................................................................................................... 17
2.3.8
Storage ............................................................................................................. 18
2.4
ENVIRONMENTAL PROTECTION ........................................................................... 18
2.4.1
ISO 14001 certification .................................................................................... 18
2.4.2
Recycling of packing materials ...................................................................... 18
2.4.3
Device disposal ............................................................................................... 18
3
INSTALLATION................................................................................ 19
3.1
RECEIPT OF THE UPS ............................................................................................ 19
Descrizione
Rev.
Description
A
Emissione / First issue
KEOR HPE UPS 200 KVA
KEOR HPE 200 KVA
Data
Date
27.02.2017
Emesso
Approvato
Issued
Approved
R. Soldani
G. Senesi
Lingua
Pagina
di Pag.
Language
Page
of Pag.
E/I
1
87
Codice / Code
OMP06144

Advertisement

Table of Contents
loading

Summary of Contents for LEGRAND KEOR HPE UPS 200 KVA

  • Page 1: Table Of Contents

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA INSTALLATION AND START-UP OF KEOR HPE UPS 200 KVA INSTALLAZIONE E AVVIAMENTO UPS KEOR HPE 200 KVA Index / Indice ENGLISH LANGUAGE ................8 SCOPE .....................
  • Page 2 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.1.1 Storage ......................19 HANDLING OF THE UPS ..................20 POSITIONING AND INSTALLATION ..............21 3.3.1 Base plan, static load and weights ..............22 3.3.2...
  • Page 3 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 2.3.3 Trasporto e movimentazione ................53 2.3.4 Installazione ..................... 54 2.3.5 Collegamento elettrico ..................55 2.3.6 Funzionamento ....................56 2.3.7 Manutenzione ....................57 2.3.8...
  • Page 4 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA PROCEDURA DI AVVIAMENTO ................79 PROCEDURA DI ARRESTO ..................83 PROCEDURA DI TRASFERIMENTO SU BYPASS MANUALE ......83 RIAVVIO DA BYPASS MANUALE ................84...
  • Page 5 Index of pictures / Indice delle figure Picture 1 – Rating plate of KEOR HPE 200 kVA ..................12 Picture 2 – Handling of the KEOR HPE UPS 200 kVA ................20 Picture 3 – Base plan ..........................22 Picture 4 – Overall dimensions ........................23 Picture 5 –...
  • Page 6 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 14 – Avvio batteria ........................... 82 Figura 15 – Connessione dell'UPS al carico ....................82 Figura 16 – Avvio completato ........................83 Figura 17 –...
  • Page 7 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA OMP06144 REV. A...
  • Page 8: English Language

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA ENGLISH LANGUAGE OMP06144 REV. A...
  • Page 9 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA OMP06144 REV. A...
  • Page 10: Scope

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA SCOPE The instructions contained in the operating manual are applicable to the UPS systems listed below. BSP06 KEOR HPE 200 kVA Storing documentation...
  • Page 11: Safety Rules And Warnings

    SAFETY RULES AND WARNINGS USE OF THE UPS Congratulations on choosing a product from Legrand for the safety of your equipment. To obtain the best performance from your KEOR HPE 200 kVA UPS system (Uninterruptible Power Supply), we suggest that you take your time to read the following manual.
  • Page 12: Ups Rating Plate

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA UPS RATING PLATE The KEOR UPS 200 kVA is provided with an identification plate containing the operation ratings. The plate is fixed in the inside of the UPS door.
  • Page 13: Special Safety Warnings

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA SPECIAL SAFETY WARNINGS 2.3.1 General warnings The UPS is provided with various stickers with indications regarding specific dangers. These stickers must be always well visible and replaced in case they are damaged.
  • Page 14: Installation

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 2.3.4 Installation The product must be installed in strict compliance with the instructions contained in the technical back-up documentation, including the present safety instructions. In particular, the...
  • Page 15: Electrical Connection

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Do not modify the device Do not modify the device in any way: this may result in damage to the equipment itself as well as to objects and persons. Maintenance and repair must be carried out by authorized personnel only.
  • Page 16: Operation

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Injury hazard due to electric shock! The device is subject to high voltages, thus all safety instructions must be scrupulously adhered to before performing any operation on the UPS: Isolate the battery via DC circuit breakers before connecting it to the UPS;...
  • Page 17: Maintenance

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 2.3.7 Maintenance Service and repairs must be carried out by skilled and authorized personnel. Before carrying out any maintenance operation, the UPS must be disconnected from AC and DC supply sources.
  • Page 18: Storage

    ENVIRONMENTAL PROTECTION 2.4.1 ISO 14001 certification Legrand is particularly sensitive to the environmental impact of its products. That is why the UPS has been manufactured with cutting-edge eco-design criteria (ISO 14001 certification). Special care was taken in using fully recyclable materials and in reducing the amounts of raw materials used.
  • Page 19: Installation

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA INSTALLATION RECEIPT OF THE UPS Please inspect the device before installing it. In case any damage is noticed from the conditions of the package and/or from the outside appearance of the equipment, contact the shipping company or your dealer immediately.
  • Page 20: Handling Of The Ups

    To handle the UPS remove the lower rear and front, insert the forks of a fork lift. The UPS can be handled from the front according to the available spaces, as shown by the following picture. KEOR HPE Picture 2 – Handling of the KEOR HPE UPS 200 kVA OMP06144 REV. A...
  • Page 21: Positioning And Installation

    Installazione e avviamento KEOR HPE UPS 200 kVA POSITIONING AND INSTALLATION The KEOR HPE UPS 200 kVA must be installed indoor, in a clean and dry room, preferably without dust or humidity infiltrations. For the environmental conditions in the place of installation, in compliance with the current legislation, please refer to the “Overall dimensions, minimum...
  • Page 22: Base Plan, Static Load And Weights

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.1 Base plan, static load and weights GLAND PLATE Picture 3 – Base plan The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and safe support.
  • Page 23: Overall Dimensions, Clearances And Ventilation

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.2 Overall dimensions, clearances and ventilation OUTLET AIR OPENINGS KEOR HPE INLET AIR OPENINGS Picture 4 – Overall dimensions Picture 5 – Clearances...
  • Page 24 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as much as possible. With regard to the minimum distances from the walls, for all of the UPS sizes the same installation conditions apply as indicated in the table below.
  • Page 25: Environmental Installation Conditions

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.3 Environmental installation conditions The air is classified by the EN 60721-3-3 standard (Classification of environmental parameters and their severities – Stationary use at weather-protected locations) based on climatic and biological conditions as well as on mechanically and chemically active substances.
  • Page 26 Places located in industrial installations. Emissions of highly concentrated chemical pollutants The KEOR HPE UPS 200 kVA is designed to be installed in an environment that meets the following classifications. In accordance with the technical Climatic conditions specification...
  • Page 27: Positioning And Connection Of The Batteries

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA POSITIONING AND CONNECTION OF THE BATTERIES Risk of electric shock A battery can present a risk for electrical shock and high short circuit current. The following precautions should be observed when working on batteries: Remove watches, rings or other metal objects;...
  • Page 28: Electrical Connection

    All the operations related to the electric connection must be carried out by qualified and trained personnel. Work in compliance with the local standards The installation of the KEOR HPE UPS 200 kVA must be carried out in compliance with national and local regulations. Connection of ground cable The grounding of the UPS via the relevant terminal is mandatory.
  • Page 29: Connection Of The Power Cables

    UPS to the mains. CONNECTION OF THE POWER CABLES For the electric connection of the KEOR HPE UPS 200 kVA, connect the following cables: DC supply from the battery (if the battery is external); AC supply from the rectifier and bypass supply mains;...
  • Page 30 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Details of the electrical connections Power (kVA) Input fuses [A] Rectifier Bypass Phase conductor cross sect. [mm Rectifier 1x 150 Bypass 1x 120...
  • Page 31: Backfeed Protection Device

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA BACKFEED PROTECTION DEVICE The KEOR HPE UPS is provided with voltage-free contacts which can be used to operate the shunt trip coil (undervoltage release type) of the external sectioning device; the external device is not part of the UPS supply and is provided and installed at customer care.
  • Page 32: Terminal Boards

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA TERMINAL BOARDS The KEOR HPE UPS 200 kVA is provided with terminal boards for the connection of power cables and of auxiliary connections. INGRESSO RADDRIZZATORE - RECTIFIER INPUT...
  • Page 33: Battery

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA BATTERY CAUTION A battery can present a risk for electrical shock and high short circuit current. The following precautions should be observed when working on batteries: Remove watches, rings or other metal objects;...
  • Page 34: Connection Of The Auxiliary Cables

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA CONNECTION OF THE AUXILIARY CABLES The UPS systems of the KEOR HPE 200 kVA line can be connected to external controls/components specifically designed to improve the safety and reliability of the device.
  • Page 35: Remote Emergency Power Off (Epo)

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 4.5.4 Remote emergency power off (EPO) Auxiliary EPO contact on terminals X10-7/8. The voltage supply to the loads can be interrupted from a remote location by using this contact (i.e.
  • Page 36 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA RS232/USB: it is used for connection to the proprietary programming and control software. SRC-2 (OPTIONAL): relay card, used for the remote signalisations of status and alarms.
  • Page 37: Relay Card Connection (Optional)

    Installazione e avviamento KEOR HPE UPS 200 kVA RELAY CARD CONNECTION (OPTIONAL) The KEOR HPE UPS 200 kVA, in its full configuration, is provided with a relay card for repeating alarms and operating statuses remotely. The electric connection is carried out directly on the terminals located on the front of the interfaces slot SRC-2.
  • Page 38: Startup And Shutdown

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA STARTUP AND SHUTDOWN Read the technical documentation Before installing and using the device, make sure you have read and understood all the instructions contained in the present manual and in the technical supporting documentation.
  • Page 39: Start-Up Procedure

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA START-UP PROCEDURE EPO push-button and phase rotation Before switching the UPS on, make sure that: the emergency power off “EPO” push-button, if installed, is not pressed. If not, press it back to the rest position;...
  • Page 40: Picture 10 – Ups Start-Up

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Close the rectifier input switch RCB. After some seconds the touch screen will start and will show the UPS mimic diagram. Picture 10 – UPS start-up page After the software loading phase the control logic will acquire the system status and the operation of the RCB switch, and will show the operating sequences.
  • Page 41: Picture 12 – Inverter Start-Up

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Picture 12 – Inverter start-up As the inverter is correctly started-up, close the bypass switch SBCB when indicated by the display. The logic will check the correctness of the bypass phase sequence and RMS voltage value.
  • Page 42: Picture 14 – Battery Start-Up

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Picture 14 – Battery start-up Operation on BCB switch The switch BCB, located in the external battery cabinet, can only be closed if the DC voltage is in tolerance.
  • Page 43: Shut-Down Procedure

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Picture 16 – Start-up end SHUT-DOWN PROCEDURE Open the switch OCB. Open the switch BCB. Open the switch RCB. Open the switch SBCB.
  • Page 44: Restart From Manual Bypass

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA RESTART FROM MANUAL BYPASS Before restarting the UPS from manual by-pass, make sure the “Bypass_Sw" selector is in BYPASS position and the MBCB isolator is closed.
  • Page 45: Picture 19 – Connecting The Battery

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Close the battery switch BCB when indicated by the display. Picture 19 – Connecting the battery Close the output switch OCB when required and immediately after the display will require to open the manual bypass switch MBCB.
  • Page 46: Picture 21 – Opening The Manual Bypass Switch

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Picture 21 – Opening the manual bypass switch Picture 22 – Inverter start-up As soon as the inverter is started it will be possible to transfer the load. Move the bypass switch as required by the display to complete the UPS start-up.
  • Page 47: Picture 23 – Transferring The Load

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Picture 23 – Transferring the load Picture 24 – Re-start from manual bypass completed OMP06144 REV. A...
  • Page 48: Lingua Italiana

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA LINGUA ITALIANA OMP06144 REV. A...
  • Page 49 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA OMP06144 REV. A...
  • Page 50: Applicabilita

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA APPLICABILITA’ Le istruzioni riportate nel manuale operativo sono applicabili ai gruppi di continuità elencati di seguito. BSP06 KEOR HPE 200 kVA Conservazione della documentazione...
  • Page 51: Regole E Avvertenze Di Sicurezza

    REGOLE E AVVERTENZE DI SICUREZZA UTILIZZO DEL DISPOSITIVO Complimenti per aver scelto un prodotto della Legrand per la sicurezza delle vostre apparecchiature. Per usufruire al meglio delle prestazioni del vostro UPS KEOR HPE 200 kVA (gruppo statico di continuità) vi suggeriamo di dedicare il tempo per la lettura del seguente manuale.
  • Page 52: Dati Nominali Ups

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA DATI NOMINALI UPS L’UPS KEOR HPE 200 kVA è provvisto di una targhetta di identificazione che riporta i dati nominali di funzionamento. La targhetta è fissata nella parte interna della porta frontale.
  • Page 53: Indicazioni Particolari Sulla Sicurezza

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA INDICAZIONI PARTICOLARI SULLA SICUREZZA 2.3.1 Avvertenze generali L’UPS è provvisto di una serie di targhette adesive con indicazioni sui pericoli specifici; tali targhette devono sempre essere ben visibili e sostituite in caso di danneggiamento.
  • Page 54: Installazione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 2.3.4 Installazione L’installazione del prodotto deve essere effettuata seguendo scrupolosamente le indicazioni riportate nella documentazione tecnica di supporto, incluse le presenti indicazioni sulla sicurezza.
  • Page 55: Collegamento Elettrico

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Non effettuare modifiche al dispositivo effettuare nessuna modifica dispositivo, potrebbe causare danni all'apparecchiatura stessa ed a cose e persone. La manutenzione e le riparazioni devono essere eseguite solamente da personale autorizzato.
  • Page 56: Funzionamento

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Pericolo di lesioni a seguito shock elettrico Il dispositivo è soggetto a tensioni elevate, è quindi necessario seguire scrupolosamente le direttive sulla sicurezza prima di effettuare qualsiasi lavoro sull’UPS:...
  • Page 57: Manutenzione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 2.3.7 Manutenzione La manutenzione e le riparazioni devono essere effettuate da personale esperto ed autorizzato. Prima di effettuare qualsiasi intervento di manutenzione l’UPS deve essere disconnesso dalle sorgenti di alimentazione DC e AC.
  • Page 58: Immagazzinamento

    TUTELA AMBIENTALE 2.4.1 Certificazione ISO 14001 Legrand è particolarmente sensibile all’impatto ambientale dei propri prodotti, per questo motivo l'UPS è stato realizzato seguendo i più moderni criteri di eco-progettazione (certificazione ISO 14001). E' stata prestata particolare attenzione nell’utilizzo di materiali completamente riciclabili e nella riduzione della quantità...
  • Page 59: Installazione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA INSTALLAZIONE RICEZIONE DELL’UPS Si prega di ispezionare il dispositivo prima di procedere all'installazione. Se dalle condizioni dell'imballaggio e/o dall'aspetto esterno dell'apparecchiatura si rileva un qualunque danno, contattare immediatamente la società...
  • Page 60: Movimentazione Dell'ups

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA MOVIMENTAZIONE DELL’UPS L’UPS viene imballato su pallet; la movimentazione dal mezzo di trasporto al luogo di installazione (o di stoccaggio) viene effettuata per mezzo di carrello elevatore.
  • Page 61: Posizionamento Ed Installazione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA POSIZIONAMENTO ED INSTALLAZIONE L’UPS KEOR HPE 200 kVA deve essere installato all’interno, in una stanza asciutta e pulita, possibilmente priva di infiltrazioni di polvere ed umidità. Per quanto riguarda le condizioni ambientali nel luogo di installazione, in accordo alle normative correnti, fare riferimento alla sezione “Dimensioni di ingombro, distanze minime dalle pareti e ventilazione”.
  • Page 62: Pianta Di Base, Carico Statico E Pesi

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.1 Pianta di base, carico statico e pesi PIASTRA INGRESSO CAVI Figura 3 – Pianta di base La base di appoggio dell’UPS deve essere progettata per sopportare il peso del dispositivo e per garantirne il supporto saldo e sicuro.
  • Page 63: Dimensioni Di Ingombro, Distanze Minime Dalle Pareti E Ventilazione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.2 Dimensioni di ingombro, distanze minime dalle pareti e ventilazione APERTURE USCITA ARIA KEOR HPE APERTURE INGRESSO AREA Figura 4 – Dimensioni di ingombro Figura 5 –...
  • Page 64 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA L’ UPS deve essere installato in maniera da garantirne l’ispezionabilità e favorire per quanto possibile il corretto flusso di aria. Per tutte le taglie di UPS valgono le stesse condizioni di installazione per quanto riguarda le distanze minime dalle pareti, come indicate nella tabella seguente.
  • Page 65: Condizioni Ambientali Di Installazione

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 3.3.3 Condizioni ambientali di installazione L’aria viene classificata dalla norma EN 60721-3-3 (Classificazione dei parametri ambientali e loro severità – Uso in posizione fissa in luoghi protetti dalle intemperie), sulla base delle condizioni climatiche, biologiche e delle sostanze meccanicamente e chimicamente attive.
  • Page 66 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Classificazione delle sostanze chimicamente attive (EN 60721-3-3) Classe Parametro ambientale 3C1R 3C1L Nebbia Nebbia Nebbia j) Sali marini salina salina salina k) Anidride solforosa [mg/m...
  • Page 67: Posizionamento E Allacciamento Batterie

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA POSIZIONAMENTO E ALLACCIAMENTO BATTERIE Pericolo di lesioni a seguito shock elettrico Una batteria può costituire un rischio di scossa elettrica e di un’elevata corrente di cortocircuito.
  • Page 68: Allacciamento Elettrico

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA ALLACCIAMENTO ELETTRICO L’allacciamento elettrico rientra normalmente nelle competenze della azienda che esegue l’installazione del prodotto, e il costruttore dell’UPS non può essere ritenuto responsabile per eventuali danni dovuti a collegamenti errati.
  • Page 69: Collegamento Conduttori Di Potenza

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Allacciamento alla rete L’allacciamento alla rete deve essere fatto interponendo fra questa e l’UPS dei fusibili di protezione. E’ sconsigliato l’utilizzo di dispositivi di protezione differenziali nella linea di alimentazione dell’UPS;...
  • Page 70 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Pericolo di danni al dispositivo a seguito cablaggio errato Per effettuare il collegamento del dispositivo seguire scrupolosamente lo schema elettrico e rispettare la polarità dei cavi.
  • Page 71: Protezione Contro Il Ritorno Di Tensione (Backfeed)

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA PROTEZIONE CONTRO IL RITORNO DI TENSIONE (BACKFEED) L'UPS KEOR HPE è provvisto in opzione di contatti liberi da tensione per il pilotaggio di una bobina di minima tensione del dispositivo di sezionamento esterno (a carico dell'installazione).
  • Page 72: Morsettiere

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA MORSETTIERE L’UPS KEOR HPE 200 kVA è provvisto di morsettiere per l’allacciamento dei cavi di potenza e delle connessioni ausiliarie. INGRESSO RADDRIZZATORE - RECTIFIER INPUT...
  • Page 73: Installazione Batterie

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA INSTALLAZIONE BATTERIE ATTENZIONE Una batteria può costituire un rischio di scossa elettrica e di un’elevata corrente di cortocircuito. Quando si opera sulle batterie devono essere osservate le seguenti precauzioni: Rimuovere orologi da polso, anelli e altri oggetti metallici;...
  • Page 74: Collegamento Cavi Ausiliari

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA COLLEGAMENTO CAVI AUSILIARI Gli UPS della linea KEOR HPE 200 kVA possono essere collegati con controlli / componenti esterni appositamente previsti per migliorare la sicurezza e l’affidabilità del dispositivo.
  • Page 75: Spegnimento Remoto (Epo)

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA 4.5.4 Spegnimento remoto (EPO) Contatto ausiliario di EPO; morsetti X10-7/8. L’alimentazione ai carichi può essere interrotta da una postazione remota utilizzando questo contatto (es. per requisiti di sicurezza). Un contatto normalmente chiuso deve essere connesso ai terminali dell’UPS (EAC1-EAC2);...
  • Page 76 Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA RS232/USB: utilizzata collegamento software proprietario programmazione e controllo. SRC-2 (OPZIONALE): scheda relè, utilizzata per la ripetizione a distanza di stati di funzionamento e allarmi.
  • Page 77: Collegamento Scheda Relè (Opzionale)

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA COLLEGAMENTO SCHEDA RELÈ (OPZIONALE) L’UPS KEOR HPE 200 kVA, nella sua configurazione completa, è provvisto di una scheda relè per la ripetizione remota di stati di funzionamento e allarmi. Il collegamento elettrico è realizzato direttamente sui morsetti sul fronte dello slot di interfaccia SRC-2.
  • Page 78: Avviamento E Arresto

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA AVVIAMENTO E ARRESTO Leggere la documentazione tecnica Prima di installare ed utilizzare l'apparecchiatura, assicurarsi di aver letto e compreso tutte le istruzioni contenute nel presente manuale e nella restante documentazione tecnica di supporto.
  • Page 79: Procedura Di Avviamento

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA PROCEDURA DI AVVIAMENTO Pulsante EPO e senso ciclico fasi Prima di avviare l’UPS, verificare che: il pulsante di arresto di emergenza “EPO”, se installato, non sia premuto; in caso contrario riportarlo nella posizione di riposo;...
  • Page 80: Figura 10 – Schermata Avvio Ups

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Chiudere il sezionatore di ingresso raddrizzatore RCB. Dopo alcuni secondi il touch screen si avvierà e mostrerà il diagramma sinottico dell'UPS. Figura 10 – Schermata avvio UPS Dopo la fase di caricamento del software la logica di controllo acquisisce lo stato del sistema a seguito della chiusura di RCB e mostra le sequenze di avviamento.
  • Page 81: Figura 12 – Avvio Inverter

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 12 – Avvio inverter Appena l'inverter è correttamente avviato chiudere il sezionatore SBCB quando indicato dal display. La logica controlla che la sequenza fasi e il valore RMS della tensione di bypass siano corrette.
  • Page 82: Figura 14 - Avvio Batteria

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 14 – Avvio batteria Chiusura sezionatore BCB La chiusura del sezionatore BCB, posto nell'armadio esterno, può essere effettuata solamente se la tensione DC è in tolleranza. Se effettuata prima che venga richiesta dal pannello frontale, può...
  • Page 83: Procedura Di Arresto

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 16 – Avvio completato PROCEDURA DI ARRESTO Aprire il sezionatore OCB. Aprire il sezionatore BCB. Aprire il sezionatore RCB. Aprire il sezionatore SBCB.
  • Page 84: Riavvio Da Bypass Manuale

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA RIAVVIO DA BYPASS MANUALE Prima di riavviare l’UPS da bypass manuale, controllare che il selettore “Bypass_Sw” sia in posizione BYPASS e il sezionatore MBCB Chiuso.
  • Page 85: Figura 19 - Connessione Della Batteria

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Chiudere il sezionatore di batteria BCB quando indicato dal display. Figura 19 – Connessione della batteria Chiudere il sezionatore OCB quando richiesto; immediatamente dopo il display richiederà...
  • Page 86: Figura 21 - Apertura Del Sezionatore Di Bypass Manuale

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 21 – Apertura del sezionatore di bypass manuale Figura 22 – Avvio inverter Appena l'inverter è correttamente avviato sarà possibile trasferire il carico. Muovere il selettore Bypass-SW come richiesto per completare l'avviamento dell'UPS.
  • Page 87: Figura 23 - Trasferimento Del Carico

    Installation and start-up of KEOR HPE UPS 200 kVA Installazione e avviamento KEOR HPE UPS 200 kVA Figura 23 – Trasferimento del carico Figura 24 – Avvio da bypass manuale completato OMP06144 REV. A...