Delta Electronics INX-1K User Manual page 20

Inx series, single phase 1/2/3 kva
Table of Contents

Advertisement

04: ECO enable/ disable
z
z
Parameter 3: Enable or disable ECO function. You may choose the following
two options.
ENA: ECO mode enable
DIS: ECO mode disable (Default)
05: ECO voltage range setting
z
z
Parameter 2 & 3: Set the acceptable high voltage point and low voltage point
for ECO mode by pressing the Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from +7V to +24V of the nominal voltage.(Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from -7V to -24V of the nominal voltage. (Default: -12V)