Code
Name
Product code
(Function)
Thermistor
TH3
TH4
(Liquid level
detection)
TH5
(Pipe
temperature)
TH6
(Outdoor
temperature)
TH7
(Pipe inlet
heat ex-
changer
temperature)
TH9
TH10
THHS inverter
heat sink tem-
perature
Solenoid
SV1
valve
discharge-
suction
bypass
SV22
capacity
control (full
load)
SV32
capacity
control
(unload)
SV4a
discharge-
suction
bypass
Application
Detects liquid level of refrigerant inside
accumulator using the differences
among TH2, TH3, TH4.
1 Frequency control.
2 Controls defrosting during heating.
1 Detects the outdoor air temperature.
2 Performs fan control, liquid level
heater control, opening settings of
LEV for oil return, and other functions.
Controls defrosfing during heating
1) Detects the CS circuit fluid tempera-
ture.
2) Calculates the refrigerant circulation
configuration.
1) Detects the compressor shell
temperature.
2) Provides compressor shell over-
heating protection.
Inverter cooling fan control using THHS
temperature.
1 Capacity control of high/low
pressure bypass when starting and
stopping.
2 Discharge pressure rise suppression.
Switching of capacity control valve inside
No. 2 compressor (Switching between full
load operation and unload operation)
(only P500).
Capacity control and controlling the rise
of high-pressure (Back-up of frequency
control).
–57–
Specification
R
= 15 kΩ
0
B
= 3460
1/80
Rt =
1
1
15exp{3460(
-
)}
273+t
273
0°C: 15 kΩ
10°C: 9.7 kΩ
20°C: 6.4 kΩ
25°C: 5.3 kΩ
30°C: 4.3 kΩ
40°C: 3.1 kΩ
R
= 15 kΩ
0
B
= 3460
1/80
Rt =
1
1
15exp{3460(
-
)}
273+t
273
0°C: 15 kΩ
10°C: 9.7 kΩ
20°C: 6.4 kΩ
25°C: 5.3 kΩ
30°C: 4.3 kΩ
40°C: 3.1 kΩ
R
= 7.465 kΩ
120
B
= 4057
25/120
Rt =
7.465exp
1
1
{4057(
-
)}
273+t
273+120
20°C: 250 kΩ
70°C: 34 kΩ
30°C: 160 kΩ
80°C: 24 kΩ
40°C: 104 kΩ
90°C: 17.5 kΩ
50°C: 70 kΩ 100°C: 13.0 kΩ
60°C: 48 kΩ
110°C: 9.8 kΩ
R
= 17 kΩ
50
B
= 4170
25/120
Rt =
1
1
17exp {4170 (
-
)}
273+t
323
0°C: 181 kΩ
10°C: 105 kΩ
20°C: 64 kΩ
25°C: 50 kΩ
30°C: 40 kΩ
40°C: 26 kΩ
AC 220 to 240 V
Open : conducting
Close: not conducting
AC 220 to 240 V
Close: conducting
Open : not conducting
AC 220 to 240 V
Open : conducting
Close: not conducting
Inspection method
Resistance check
Resistance check
Resistance check
Conductivity test
using tester

Advertisement