Solenoid valves (SVA, SVB, SVC, SVM1)
Coordination signals output from the board and solenoid valve operations.
Note 1 : (SVA, SVB, SVC)
SVA, SVB and SVC are turned on and off in accordance with operation mode.
Mode
Branch port
SVA
SVB
SVC
(SVM1)
SVM is turned on and off in accordance with operation mode.
Operation Mode
Cooling-only
SVM1
Note 2 : (SVA, SVB, SVC)
Measure temperature of piping on either side of SVA 1-A
Measure temperature of piping on either side of SVB 1-B
B
A
4) BC controller transformer
BC Controller control board
CNTR
Red
Blue
Cooling
Heating
ON
OFF
OFF
ON
ON
OFF
Cooling-principal
Heating-only Heating-principal
ON
OFF
1
CN03
Brown
Brown
*Depending on the models, SVM is not built in.
Stopped
OFF
OFF
OFF
Defrosting
OFF
OFF
(SVM1)
Measure temperature at points marked with an "X".
CNTR(1)-(3)
Approximately 90Ω
CN03(1)-(3)
Approximately 1.7Ω