Download Print this page

Mitsubishi Electric FX3S-30MT/ES-2AD Hardware Manual page 4

Melsec-f fx3s-30m series
Hide thumbs Also See for FX3S-30MT/ES-2AD:

Advertisement

4.6 Transistor output specifications and example of external
wiring
For details, refer to the following manual.
→ Refer to FX
3S
Series User's Manual - Hardware Edition.
4.6.1
Transistor output specifications
Item
Specification
Number of output points
14 points
Output connecting type
Fixed terminal block (M3 screw)
FX
3S
-30MT/ES-2AD
Transistor (Sink)
Output
form
FX
-30MT/ESS-2AD
Transistor (Source)
3S
External power supply
5-30 V DC
*1
Resistance load
0.5 A/point
Max. load
*2
Inductive load
12 W/24 V DC
Open circuit leakage current
0.1 mA or less/30 V DC
ON voltage
1.5 V or less
5 μs or less/10 mA or more
Y000, Y001
(5-24 V DC)
Response
OFF→ON
time
ON→OFF
0.2 ms or less/200 mA or more
Y002 to Y015
(at 24 V DC)
Output circuit insulation
Photocoupler insulation
LED on panel lights when
Output operation display
photocoupler is driven.
*1 The total load current of resistance loads per common terminal should be
the following value.
- 1 output point/common terminal: 0.5 A or less
- 4 output points/common terminal: 0.8 A or less
As for the number of outputs per common terminal, refer to "Chapter 5
interpretation of partition" and the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3S
*2 The total of inductive loads per common terminal should be the following
value.
- 1 output point/common terminal: 12 W or less/24 V DC
- 4 output points/common terminal: 19.2 W or less/24 V DC
As for the number of outputs per common terminal, refer to "Chapter 5
interpretation of partition" and the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3S
4.6.2
External wiring of transistor output
1. External wiring of sink output type
Load
Y000
DC power
Fuse
supply
COM0
Main unit
2. External wiring of source output type
Load
Y000
DC power
Fuse
supply
+V0
Main unit
4.6.3
Cautions in external wiring
As for the details of cautions in external wiring, refer to the following manual.
→ Refer to FX
3S
Series User's Manual - Hardware Edition.
5. Terminal block layouts
For details on the terminal block layout, refer to the following manual.
→ Refer to FX
3S
Series User's Manual - Hardware Edition.
Interpretation of partition
The partition of the output terminals (see following figure) indicates the range of
the output connected to the same common.
Example: FX
-30MT/ES-2AD
3S
Output terminal
0V
Y0
Y1
24V
COM0
COM1
Partition
6. Built-in analog specifications and wiring
For details on the built-in analog input specifications and wiring, refer to
following manual.
→ Refer to FX
3S
Series User's Manual - Hardware Edition.
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
WIRING
PRECAUTIONS
• Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the power line or shield of the analog input/output
cable together with or lay it close to the main circuit, high-voltage line,
or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100 mm (3.94") or
more away from the main circuit, high-voltage line, or load line.
2) Ground the shield of the analog input/output cable at one point on the
signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-
circuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric
wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the
connected parts are directly stressed.
6.1 Analog input terminal block (European type)
1) Wire size
Wiring to analog device should use wire from following table.
Wire size
No. of wire per
Ferrules with
terminal
Solid wire
Stranded wire
plastic sleeve
2
2
0.14 to 1.5 mm
0.14 to 1.0 mm
0.25 to 0.5 mm
1
(AWG26 to 16)
(AWG26 to 16)
(AWG24 to 20)
2
2
0.14 to 0.5 mm
0.14 to 0.2 mm
2
(AWG26 to 20)
(AWG26 to 24)
2) Termination
Strip the coating of strand wire and twist the cable core before connecting
it, or strip the coating of single wire before connecting it. An alternative
connection is to use a ferrule with insulating sleeve.
Manufacturer
Model
AI 0.25-6BU (AWG24)
Phoenix Contact
AI 0.34-6TQ (AWG22)
Co., Ltd.
AI 0.5-6WH (AWG20)
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
• Stranded wire/solid wire
• Ferrule with insulation sleeve
Termination of
Insulating sleeve
cable end
Approx.
5 mm
(0.19")
2 to 2.5 mm
(0.07" to 0.09")
When using a ferrule with insulation sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, otherwise the wire
cannot be inserted easily.
Tighten the screws to a torque of 0.22 to 0.25 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned
range. Failure to do so may cause equipment failures or malfunctions.
3) Tool
For tightening the terminal, use a
c o m m e r c i a l l y a v a i l a b l e s m a l l
screwdriver having a straight form that
is not widened toward the end as
0.4 mm
shown right.
(0.01")
Caution:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in
the table above, use the following screwdriver or appropriate replacement
(grip diameter : approximately 25 mm (0.98")).
Manufacturer
Phoenix Contact Co., Ltd.
6.2 Analog input specifications and external wiring
6.2.1
Analog input performance specifications
Item
Input specification
Analog input range
0-10 V DC (Input resistance: 115.7 kΩ)
Absolute maximum input -0.5 V, +15 V
Digital output
10 bits, binary
D8270 (The digital value of CH1 is stored)
Device allocation
D8271 (The digital value of CH2 is stored)
Resolution
10 mV (10 V/1000)
- ± 1.0 % (± 100 mV) for 10 V full scale
(when ambient temperature is 25 ± 5 °C)
Total accuracy
- ± 2.0 % (± 200 mV) for 10 V full scale
(when ambient temperature is 0 to 55 °C)
180 μs
A/D conversion time
(The data will be updated at every scan time of the PLC.)
1020
1000
Input characteristics
0
10V
Analog input
Insulation method
No insulation between each channel or the PLC.
0 point
2
Occupied points
(This number is not related to the maximum number
of input/output points of the PLC.)
-
6.2.2
Example of analog input
Caulking tool
*1
Grounding
CRIMPFOX 6
*2
(or CRIMPFOX 6T-F
)
V +, ch
:
represents the channel number.
*1 Use the 2-core shielded twisted pair cable for the analog input lines, and
separate the analog input lines from other power lines or inductive lines.
*2 Make sure to short-circuit the "V+" and "V-" terminals when ch is not used.
Contact area
6.2.3
Analog input terminal block layouts
(Crimp area)
V1+
V2+
V-
6 mm
(0.23")
10.5 to 12 mm
(0.41" to 0.47")
「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
With
 本产品中所含有的有害 6 物质的名称, 含有量, 含有部品如下
straight tip
表所示。
2.5 mm
产品中有害物质的名称及含量
(0.09")
部件名称
(Pb)
Model name
SZS 0.4×2.5
外壳
可编程
控制器
印刷基板
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T
26572规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出
GB/T 26572规定的限量要求。
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
10.2V
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
ch
*1
82.7 k
V +
V-
33 k
*2
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
×
For safe use

Advertisement

loading

This manual is also suitable for:

Fx3s-30mr/es-2adFx3s-30mt/ess-2ad