Download Print this page

Frico Panther SE06N Original Instructions Manual page 10

Panther 6-15 kw
Hide thumbs Also See for Panther SE06N:

Advertisement

GB
General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid if the product is used
in the manner intended and in accordance
with the instructions.
Application area
Panther 6-15 is a range of very quiet and
efficient fan heaters for stationary use. They
are intended for heating and drying in e.g.
workshops, sport halls, shops, assembly
rooms and drying rooms.
Protection class: IP44.
Mounting
The fan heater is mounted on a wall with
a bracket, which allows direction of the air
stream in several directions, straight ahead,
to the left, to the right and down.
Note! The minimum distances given in fig. 2
and 3 must be kept. The fan heaters must not
be mounted on the ceiling.
• Loose the bracket from the appliance by
unscrewing the bolts.
• Mark holes by means of the loose bracket.
• Drill holes for the fixing plugs.
• Mount the bracket.
• Mount the fan heater on the bracket and
adjust the heater to desired vertical and
horizontal angles.
• Screw the bottom bolt in and tighten all
bolts.
Electrical installation
The electrical installation should be carried
out by a qualified electrician in conformity
with prevailing regulations. The appliance
should be preceded by an all-pole switch with
at least 3 mm breaking gap. There are several
ways to connect depending on the desired
function.
On delivery the appliance is equipped with
connections on the terminal block.
12
Panther 6-15
Installation and operating instructions
Factory setting
9
1
2
3
11 12
On delivery, the external thermostat controls
heat on/off. In operation, fan and output steps
are set on the control box PP15N.
With a connection between terminals 14 and
15, the fan RPM will be controlled by the
regulation and the heat by the thermostat.
Without the connection the thermostat will
control both fan RPM and heat.
When accessories are connected or when
several heaters are connected to each other
and controlled by a common accessory.
Between terminals 1 and 13, a 230V~ alarm
signal can be obtained. When the temperature
limiter is triggered, the voltage will drop to
zero.
On delivery the Panther 6 – 15 fan heaters
are for 400V3N~. SE135N can be connected
to both 440V3~ and 500V3~.
Type
Output
Voltage
[kW]
[V]
Control
0
230V~
SE06N
6
400V3N~/230V3~
SE09N
9
400V3N~/230V3~
SE12N
12
400V3N~/230V3~
15
400V3N~/230V3~
SE15N
SE135N
13,5
500V3~/440V3~
On the back of the appliance there are knock-
outs. Cable-glands used must guarantee the
protection class requirements!
When several heaters are connected to each
other and controlled by a common accessory
it should be stated in the group centre that
"The fan heaters are fed from more than one
group supply".
Control
When using this product as a local space
heater according to Ecodesign Regulation
(EU) 2015/1188, it must be supplemented
with one of the following approved controls.
• PP15N, control box and TAP16R, electronic
thermostat that include:
- Electronic room temperature control plus
14
15
Minimum
area
[mm
]
2
0,75
1,5/2,5
2,5/6
4/10
6/16
4/2,5

Advertisement

loading

This manual is also suitable for:

Panther se09nPanther se15nPanther se12nPanther se135n