Allen-Bradley PowerFlex 525 Original Instructions Manual page 24

Hide thumbs Also See for PowerFlex 525:
Table of Contents

Advertisement

PowerFlex 525 AC Drive Specifications
Maximum Control Wire Recommendation
Do not exceed control wiring length of 30 m (100 ft). Control signal cable length is highly dependent on electrical
environment and installation practices. To improve noise immunity, the I/O terminal block Common may be connected to
ground terminal/protective earth. If using the RS485 (DSI) port, I/O Terminal C1 should also be connected to ground
terminal/protective earth. Additionally, communication noise immunity can also be improved by connecting I/O Terminal
C2 to ground terminal/protective earth.
Control I/O Terminal Block Wire Specifications
Frame
Maximum Wire Size
2
A...E
1.3 mm
(16 AWG)
(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.
Machinery Directive (2006/42/EC)
• EN ISO 13849-1:2008 – Safety of machinery – Safety related parts of control systems -Part 1: General principles for
design.
• EN ISO 13849-2:2008 – Safety of machinery – Safety related parts of control systems -Part 2: Validation.
• EN 62061:2005 – Safety of machinery – Functional safety of safety-related electrical, electronic and programmable
electronic control systems.
• EN 60204-1:2006 – Safety of machinery – Electrical equipment of machines - Part 1: General requirements.
• EN 61800-5-2:2007 – Adjustable speed electrical power drive systems - Part 5-2: Safety requirement – Functional.
Connections and Grounding
Shielded enclosure (1)
EMI filter
L1
L2
L3
Enclosure ground connection
Building structure steel
(1) Some installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the EMI filter.
PowerFlex 525 RF Emission Compliance and Installation Requirements
Standard/Limits
EN61800-3 Category C1
EN61000-6-3
Filter Type
CISPR11 Group 1 Class B
Internal
(1)
External
30 m (16 ft)
(1) See
Accessory Dimensions on page 37
24
(1)
Minimum Wire Size
0.13 mm
IP 30/NEMA 1/UL Type 1
Esc
Sel
option kit or EMC kit
EMI fittings and metal conduit
R/L1
L1'
S/L2
L2'
T/L3
L3'
Shielded motor cable
for more information on optional external filters.
Rockwell Automation Publication 520-TD001B-EN-E - June 2013
(1)
2
(26 AWG)
U/T1
V/T2
W/T3
EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power ≤ 20 kVA)
10 m (33 ft)
100 m (328 ft)
Torque
0.71...0.86 Nm (6.2...7.6 lb-in.)
EN61800-3 Category C3 (I ≤ 100 A)
CISPR11 Group 1 Class A
(Input power > 20 kVA)
20 m (66 ft)
100 m (328 ft)

Advertisement